Permit Information
Permit NumberELE19-01489
StatusFinaled
Name R M E INC
Site Address 3500 N CABARTON LN
Project Name 
Customer Number 
ePlanReviewNo
Description
New: Install 1200A 277/480V service with connections to lights, outlets and mechanical equipment including site development for new elementary school.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final8/6/20208/7/20208/7/2020APASS
DetailsTom Saunders
Randy is the contact. Phone #: ###-#### Inspection requested via web by Buster Bowen...

job complete...ok to final
Electrical Rough-In7/7/20207/8/20207/8/2020APASS
DetailsTom Saunders
Underground cover. Phone #: ###-#### Inspection requested via web by Buster Bowen...
parking lot underground...ok to cover
Electrical Rough-In7/2/20207/2/20207/2/2020PPASS
DetailsTom Saunders
Underground cover. North side of demo''d building. Trenching for parking lot pole lights. Phone #: ###-#### Inspection requested via web by Buster Bowen...
main entry off Cabarton...1st half ok to cover
Electrical Rough-In5/21/20205/22/20205/22/2020APASS
DetailsTom Saunders
Underground Cover. Jesse is the contact Phone #: ###-#### Inspection requested via web by Buster Bowen...ok to cover...temp power for job trailer, future power for parking lot lights, and car charger station
Electrical Rough-In5/19/20205/20/20205/20/2020PCANC
DetailsTom Saunders
Underground Cover. Jesse is the onsite contact. Phone #: ###-#### >> Inspection requested via web by Buster Bowen Inspection cancelled from web by: Buster Bowen
Final4/23/20204/23/20204/23/2020PPART
DetailsTom Saunders
Final on roof top units. Please call Justin 1/2 prior to arrival. ###-#### Phone #: ###-#### Inspection requested via web by Buster Bowen...

temp occupency given...
exterior cans installed
leaving permit open for HVAC unit disconnects need required labelling and parking lot light poles need completion
Final4/9/20204/10/20204/10/2020APART
DetailsTom Saunders
Partial Final Kitchen. Randy is the contact. Phone #: ###-#### Inspection requested via web by Buster Bowen...
kitchen complete
Final4/6/20204/6/20204/6/2020PNR
DetailsTom Saunders
Kitchen/Misc final. Jesse is the contact. Phone #: ###-#### Inspection requested via web by Buster Bowen...
no electrician on site...walked with general
kitchen not complete...GFCI protection all 120V outlets...freezer disconnect for inside cooler...kitchen panel needs labelling completion
electrical rm open junction box...access to panels
exterior lighting missing 5 cans
GYM storage rm complete
need to do rooftop units...need electrician onsite
Final3/30/20203/31/20203/31/2020APART
DetailsTom Saunders
area C & D // Buster Phone #: ###-####...
Area C classrooms, storage, and restrooms
Area D classrooms, storage
Gym...interior
Final3/27/20203/30/20203/30/2020APART
DetailsTom Saunders
Final in Areas A and B. Jesse is the onsite contact. Phone #: ###-#### Inspection requested via web by Buster Bowen...
Area A offices and classrooms
Area B classrooms
Area C library only
Electrical Rough-In3/10/20203/11/20203/11/2020APASS
DetailsTom Saunders
Area D canopy cover. Toby is the contact Phone #: ###-#### Inspection requested via web by Buster Bowen...ok to cover
Electrical Rough-In2/21/20202/21/20202/21/2020PPASS
DetailsEric Story
Toby. Canopy cover. Phone #: ###-#### Inspection requested via web by Sean DeLacy
Canopys (minus 1) ok to cover
U/G south end lots and accross ok to cover
Electrical Rough-In2/13/20202/13/20202/13/2020PPASS
DetailsTom Saunders
Kitchen ceiling cover. Toby is the contact Phone #: ###-#### Inspection requested via web by Buster Bowen...ok to cover...cooler area ceiling will need future inspection
Electrical Rough-In2/12/20202/13/20202/13/2020ACANC
DetailsTom Saunders
Kitchen ceiling cover. Toby is the contact Phone #: ###-#### Inspection requested via web by Buster Bowen...no access...scheduled to PM
Electrical Rough-In2/12/20202/12/20202/12/2020ANR
DetailsTom Saunders
Kitchen ceiling cover. Toby is the contact Phone #: ###-#### Inspection requested via web by Buster Bowen...not ready...call when complete...open connections, stubs, boxes...other subs need completetion first
Electrical Rough-In1/29/20201/30/20201/30/2020PPASS
DetailsRock A. Hudson
Ceiling/Canopy covers in area A and D. Toby is the contact. Phone #: ###-#### Inspection requested via web by Buster Bowen
Area (A) canopy and area (D) south grid rough in ok cover.
Electrical Rough-In1/6/20201/7/20201/7/2020APASS
DetailsTom Saunders
Ceiling cover in area C, area A;B corridors,and misc in area A. Toby is the contact. Phone #: ###-#### Inspection requested via web by Buster Bowen...grid ok to cover...as marked on plans
last classroom verify blanks and junction at next grid inspection
Electrical Rough-In11/25/201911/26/201911/26/2019APASS
DetailsTom Saunders
Ceiling cover in area A. Toby is the contact. Phone #: ###-#### Inspection requested via web by Buster Bowen...grid marked on plans
Electrical Rough-In11/20/201911/20/201911/20/2019PPASS
DetailsEric Story
Ceiling cover. Toby is the contact Phone #: ###-#### Inspection requested via web by Buster Bowen
Suspended ceilings and hard lids as noted on print ok to cover
Electrical Rough-In11/5/201911/5/201911/5/2019PPASS
DetailsTom Saunders
Ceiling cover... Toby is the contact. Phone #: ###-#### Inspection requested via web by Buster Bowen...grid as marked on plans...bathrooms, vestibules
Permanent Service11/5/201911/5/201911/5/2019PPASS
DetailsTom Saunders
Toby is the contact Phone #: ###-#### Inspection requested via web by Buster Bowen...
GFCI tested and verified and AFC label done
p/s u/g move to new location ok when requested
Permanent Service10/31/201910/31/201910/31/2019PCANC
DetailsRock A. Hudson
Toby is the contact Phone #: ###-#### Inspection requested via web by Buster Bowen As per phone call to 363 need to cancel and will recall Tuesday
Permanent Service10/30/201910/31/201910/31/2019ACANC
DetailsTom Saunders
Toby is the contact Phone #: ###-#### Inspection requested via web by Buster Bowen...
working on paperwork and info of testing of OCPD
Permanent Service10/29/201910/30/201910/30/2019ANR
DetailsTom Saunders
Toby is the contact Phone #: ###-#### Inspection requested via web by Buster Bowen...
needing AFC label before ok given
panels have been verified and able to close up and cover
Electrical Rough-In10/29/201910/30/201910/30/2019APASS
DetailsTom Saunders
Wall cover in area D. Toby is the contact Phone #: ###-#### Inspection requested via web by Buster Bowen...arrea D North walls...marked on plans ok to cover
Electrical Rough-In10/18/201910/21/201910/21/2019APASS
DetailsMark Moncarr
Wall cover in area D. Toby is the contact. Phone #: ###-#### Inspection requested via web by Buster Bowen Ok cover Area D walls. Highlighted and noted on prints.
Electrical Rough-In9/30/201910/1/201910/1/2019PPASS
DetailsTom Saunders
Wall cover area C. Dave is the contact Phone #: ###-#### Inspection requested via web by Buster Bowen...wall cover marked on contractors plans...adding corridor and media room
Electrical Rough-In9/30/201910/1/20199/30/2019ACANC
DetailsTom Saunders
Wall cover for Area C and Media room Phone #: ###-#### >> Inspection requested via web by Tyler Bowen Inspection cancelled from web by: Buster Bowen
Electrical Rough-In9/23/20199/24/20199/24/2019PPASS
DetailsJames Ady
Wall cover area B/C. Toby is the contact. Phone #: ###-#### Inspection requested via web by Buster Bowen Walls only as marked on contractor print
Electrical Rough-In9/18/20199/19/20199/19/2019PPASS
DetailsRock A. Hudson
Wall cover in area A. Toby is the onsite contact. Phone #: ###-#### Inspection requested via web by Buster Bowen
Some walls in Area A and firred out wall in area B as noted on contractor print rough in ok cover
Electrical Rough-In9/16/20199/17/20199/17/2019PPASS
DetailsTom Saunders
Wall cover in area A. Toby is the contact. Phone #: ###-#### Inspection requested via web by Buster Bowen....walls ok to cover...areas marked and dated on plans
Electrical Rough-In8/30/20199/4/20199/4/2019PPASS
DetailsTom Saunders
Wall cover. Toby is the contact Phone #: ###-#### Inspection requested via web by Buster Bowen...
6 classrooms walls ok...marked on plans
Electrical Rough-In5/31/20196/3/20196/3/2019PPASS
DetailsRock A. Hudson
Von. Underground. Please call prior to heading to the site. Phone #: ###-#### Inspection requested via web by Sean DeLacy

2nd concrete encased electrode added to north side of elec. rm OK. Conduit ran over to underground metal water pipe. Electrical room and kitchen underground only rough in ok cover.
Electrical Rough-In5/16/20195/17/20195/17/2019APASS
DetailsRock A. Hudson
Ufer inspection. Von is the contact Phone #: ###-#### Inspection requested via web by Buster Bowen
Construction entrance off Kingston from Cole.
Concrete encased electrode located on north east corner, 3/0, rough in ok cover