Information based on query as of Wednesday, July 24, 2024.
Permit Information
Permit NumberELE19-01669
StatusFinaled
Name BRIGHT IDEAS LIGHTING CO
Site Address 1819 N 9TH ST
Project Name 
Customer Number 
ePlanReviewNo
Description
Alteration or Repair: Upgrade permanent service on main house and do a subfeed panel to the new garage 50amps. Remove overhead service to upgrade.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final9/30/201910/1/201910/1/2019APASS
DetailsMark Moncarr
Talked to Electrician, he did not move 100a brkr yet. Rescheduled from 9/30 ###-#### Ok final.
Final9/29/20199/30/20199/30/2019PCANC
DetailsMark Moncarr
Phone #: ###-#### Inspection requested via web by Tim Dunlop Rescheduled for 10/1
Electrical Rough-In7/29/20197/29/20197/29/2019PPASS
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by Tim Dunlop
Permanent service completed in May. Sub feed to garage installed as well as 2nd ground rod installed at garage complete.
Must relocate garage breaker at meter main on house, 100 amp breaker installed on breaker space with 50 amp max rating.
Sub feed and grounding rough in ok cover.
Rough-In Permanent Service7/28/20197/29/20197/29/2019PCANC
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by Tim Dunlop
Needed rough in inspection for subfeed to garage and grounding electrode completion.
Electrical Rough-In7/15/20197/16/20197/16/2019APASS
DetailsRock A. Hudson
electrical rough in Phone #: ###-#### Inspection requested via web by Tim Dunlop 250.53- A single ground rod shall have a suppemental rod installed unless proven less that 25ohms to ground by final.
#8 SER 40amp max installed for range circuit.
Rough in ok cover
Electrical Rough-In6/19/20196/19/20196/19/2019PPASS
DetailsMark Moncarr
underground inspection for trench Phone #: ###-#### Inspection requested via web by Tim Dunlop Ok cover trench.
Rough-In Permanent Service5/30/20195/30/20195/30/2019PPASS
DetailsMark Moncarr
Phone #: ###-#### Inspection requested via web by Tim Dunlop p/s o/h n ok
Conference5/7/20195/9/20195/9/2019ADONE
DetailsMark Moncarr
Milenko Phone #: ###-#### Discussed service location for ADU