Permit NumberELE19-01749
StatusFinaled
Name MALCOLM R EMERY
Site Address 2109 S ASH PARK LN
Project NameHOUSE W/ GARAGE
Customer Number 
ePlanReviewNo
Description
Wiring for new home
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final6/12/20206/15/20206/15/2020APASS
DetailsTom Saunders
screened // Malcolm Phone #: ###-####...
corrections made..ok to final
Final6/11/20206/12/20206/12/2020AFAIL
DetailsEric Story
Screened- Malcon Phone #: ###-####
1)Max overcurrent on A/C states 25/30 installed
2)W/R resistent receptacles for outdoors
3) GFCI for recept on furnace and has reverse polarity
Electrical Rough-In5/22/20195/23/20195/23/2019APASS
DetailsRock A. Hudson
malcom Phone #: ###-####
House rough in ok cover
Electrical Rough-In5/21/20195/22/20195/22/2019AFAIL
DetailsRock A. Hudson
Malcolm Phone #: ###-####
210.11- Garage receptacle circuit shall have no other outlets. Garage lighting on with receptacles and 14 ga. wire installed as jumpers between lights and travellers in garage.
Conference5/13/20195/13/20195/13/2019PDONE
DetailsEric Story
Malcom Phone #: ###-####
Will need to verify branch circuit in which 12g ran to areas and have 14g jumpers in between is on 15amp max breaker, Isolate grounded and grounding in both panels, re-check stapling throughout house