Permit Information
Permit NumberELE19-02322
StatusFinaled
Name TDR ELECTRIC
Site Address 4321 E PARKCENTER BLVD
Project Name 
Customer Number 
ePlanReviewNo
Description
Complete Installation (includes room count and per: New
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final9/9/20199/9/20199/9/2019PPASS
DetailsJames Ady
Final inspection Final ok
Rough-In Permanent Service7/11/20197/11/20197/11/2019PPASS
DetailsJames Ady
Phone #: ###-#### Inspection requested via web by Therrin Robertson Corrections made rough in ok p/s u/g n ok
Rough-In Permanent Service7/10/20197/10/20197/10/2019AFAIL
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by Therrin Robertson
110.3- Expansion joint shall be installed as per manufacturers instructions. At time of installation joint shall be expanded to mid point to allow for expansion and contraction.
110.14- Connection to concrete encased electrode shall be tight. Loose turned with fingers.
210.52- Wall spaces 24" and wider shall have receptacle outlets installed. Up bed switch wall.
250.148- All metal boxes shall be connected to equipment grounding conductors. All equipment grounding conductors in a box shall be connected together. Complete make up.
250.68(A)- Access shall be provided to connection to concrete encased electrode. Mud ring 8" above.