Information based on query as of Wednesday, July 24, 2024.
Permit Information
Permit NumberELE19-02906
StatusFinaled
Name CAPITOL ELECTRIC
Site Address 390 S CAPITOL BLVD
Project Name 
Customer Number 
ePlanReviewNo
Description
New: Wiring for a new MOD Pizza
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final10/9/201910/10/201910/10/2019APASS
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by Jim Williams Final ok
Final10/9/201910/9/201910/9/2019PFAIL
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by Jim Williams
300.15 All boxes shall be covered. East show window receptacle, and light 15' in not in.
440.6- Over current protection shall not exceed value on name plate. 45 max 50 amp installed.
Electrical Rough-In10/4/201910/4/201910/4/2019PPASS
DetailsEric Story
Ceiling grid Phone #: ###-#### Inspection requested via web by Jim Williams
Suspended ceiling in back area of electrical area ok to cover
Electrical Rough-In9/3/20199/4/20199/4/2019APASS
DetailsRock A. Hudson
Walls only Phone #: ###-#### Inspection requested via web by Jim Williams
Walls and bathroom hardlids and dining area soffits rough in ok cover.
Electrical Rough-In8/13/20198/13/20198/13/2019PPASS
DetailsRock A. Hudson
Underground Phone #: ###-#### Inspection requested via web by Jim Williams
Service has been de-energized and moved out of what will be new bathroom. Grounding electrode conductor exended by irreversable crimp. All gear to be changed.
Under slab rough in ok cover.