Final | 10/24/2019 | 10/25/2019 | 10/25/2019 | A | PASS |
Rock A. Hudson
|
|
|
Garage code: 4141 -Furnace flex supported. -Service support at 36". -Add receptacle for appliance station in pantry. -GFCI at garage man door in tripped position. Reset and test function at front and back. Phone #: ###-#### Inspection requested via web by Dylan Pierce Final ok
|
Final | 10/23/2019 | 10/24/2019 | 10/24/2019 | A | FAIL |
Rock A. Hudson
|
|
|
Garage code is 4141. Phone #: ###-#### Inspection requested via web by Dylan Pierce 110.3- Front and rear outdoor receptacles not working. Cold. 210.52(C)- Counter top located in pantry shall have receptacle outlets installed so that no point measured along wall line is more than 24" from a receptacle outlet. 348.30- Furnace flex shall be secure with in 12" of termination. 352.30- PVC service riser shall be secured with in 3' of meter base. 440.6- AC ampacity shall not exceed value on nameplate. 25 amp max, 30 amp installed.
|
Rough-In Permanent Service | 8/16/2019 | 8/16/2019 | 8/16/2019 | P | PASS |
Daryl DeGrange
|
|
|
Changes have been made. Phone #: ###-#### Inspection requested via web by Dylan Pierce correction complete, rough-in p/s u/g n ok
|
Rough-In Permanent Service | 8/15/2019 | 8/16/2019 | 8/16/2019 | A | FAIL |