Permit Information
Permit NumberELE19-03145
StatusFinaled
Name BURKE ELECTRICAL CONTRACTING
Site Address 4203 W STATE ST
Project Name 
Customer Number 
ePlanReviewNo
Description
New: New apartments
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final7/28/20207/28/20207/28/2020PPASS
DetailsMark Moncarr
Final* Phone #: ###-#### Inspection requested via web by Kevin Burke Ok final. Asked contractor to check all ranges that GE installed. Bonding straps needed to be removed. Contractor confirmed that all straps were removed
Electrical Rough-In7/23/20207/23/20207/23/2020PPASS
DetailsMark Moncarr
Font entry ground work
Late afternoon Phone #: ###-#### Inspection requested via web by Kevin Burke Ok cover conduit for flag pole lighting,
Final7/21/20207/21/20207/21/2020PPART
DetailsMark Moncarr
4th floor units Phone #: ###-#### Inspection requested via web by Kevin Burke Partial for TCO on building. Waiting for parking lot and ground lights to be completed.
Final7/14/20207/14/20207/14/2020PPART
DetailsMark Moncarr
3rd floor Phone #: ###-#### Inspection requested via web by Kevin Burke Third floor partial. Noticed pigtails for ranges done incorrectly. Kevin said he would go through and check them. If they are not done properly, I will have the appliance company come back and re-do all and make accessible so they can be seen.
Electrical Rough-In7/8/20207/8/20207/8/2020APASS
DetailsMark Moncarr
Light pole bases Phone #: ###-#### Inspection requested via web by Kevin Burke Ok cover 4 light pole bases
Final7/2/20207/2/20207/2/2020PPART
DetailsMark Moncarr
2nd floor. Phone #: ###-#### Inspection requested via web by Kevin Burke Partial for 2nd floor rooms and classroom
Final7/1/20207/1/20207/1/2020PPART
DetailsMark Moncarr
“Final” 1st floor Phone #: ###-#### Inspection requested via web by Kevin Burke Ok final whole 1st floor
Electrical Rough-In6/19/20206/19/20206/19/2020PPASS
DetailsEric Story
4th floor ceiling Phone #: ###-#### Inspection requested via web by Kevin Burke
4th floor corridor ok to cover
Electrical Rough-In6/17/20206/17/20206/17/2020PPASS
DetailsEric Story
3rd floor grid ceiling Phone #: ###-#### Inspection requested via web by Kevin Burke
3rd floor ceiling ok to cover
Electrical Rough-In6/11/20206/11/20206/11/2020PPASS
DetailsEric Story
2nd floor corridor grid ceiling Phone #: ###-#### Inspection requested via web by Kevin Burke
2nd floor corridor suspended ceiling ok to cover
Electrical Rough-In5/29/20205/29/20205/29/2020PPASS
DetailsMark Moncarr
1st floor corridor Ceiling grid Phone #: ###-#### Inspection requested via web by Kevin Burke Ok cover 1st floor corridor ceiling
Electrical Rough-In5/21/20205/21/20205/21/2020PPASS
DetailsMark Moncarr
Hard lid ceiling in front of elevator. Phone #: ###-#### Inspection requested via web by Kevin Burke Ok cover hardlid 1st floor N side
Electrical Rough-In5/19/20205/19/20205/19/2020PPASS
DetailsMark Moncarr
Underground, communication conduits Phone #: ###-#### Inspection requested via web by Kevin Burke Ok cover ground work
Electrical Rough-In5/1/20205/1/20205/1/2020PPASS
DetailsMark Moncarr
4th floor hallway light and bathroom light/fan Phone #: ###-#### Inspection requested via web by Kevin Burke Ok cover drops in areas listed.
Electrical Rough-In4/20/20204/21/20204/21/2020APASS
DetailsEric Story
1st ; 2nd floor bathroom light and fan Phone #: ###-#### Inspection requested via web by Kevin Burke
Areas as requested ok to cover
Electrical Rough-In4/20/20204/20/20204/21/2020PPASS
DetailsMark Moncarr
3rd floor unit hallway lights Phone #: ###-#### Inspection requested via web by Kevin Burke Ok cover areas listed. Received pics from contractor due to Corona-19.
Electrical Rough-In4/15/20204/16/20204/16/2020APASS
DetailsMark Moncarr
Elevator pit/closet inspection Phone #: ###-#### Inspection requested via web by Kevin Burke Ok cover elevator pit and closet.
Electrical Rough-In4/8/20204/8/20204/8/2020PPASS
DetailsMark Moncarr
1st ; 2nd floor units hallway soffits. Phone #: ###-#### Inspection requested via web by Kevin Burke Ok cover hallway lights in 1st and 2nd floor due to fur down for HVAC.
Permanent Service3/11/20203/11/20203/11/2020PPASS
DetailsEric Story
AFC calc given is
L-L-L 3909
Main is rated at 65K
2 MAins for house panels are 10K
Permanent Service3/6/20203/9/20203/9/2020APASS
DetailsEric Story
Phone #: ###-#### Inspection requested via web by Kevin Burke
AFC calc required
p/s u/g n ok
Permanent Service3/6/20203/6/20203/6/2020ACANC
DetailsMark Moncarr
Phone #: ###-#### Inspection requested via web by Kevin Burke Waiting on parts for service.
Electrical Rough-In3/4/20203/4/20203/4/2020APASS
DetailsMark Moncarr
1st, 3rd, ; 4th floor community areas. Phone #: ###-#### Inspection requested via web by Kevin Burke Ok cover areas listed.
Electrical Rough-In2/26/20202/27/20202/27/2020APASS
DetailsMark Moncarr
4th floor units. Phone #: ###-#### Inspection requested via web by Kevin Burke Ok cover 4th floor.
Electrical Rough-In2/24/20202/24/20202/24/2020APASS
DetailsMark Moncarr
1st ; 2nd floor corridor walls. Phone #: ###-#### Inspection requested via web by Kevin Burke Ok cover areas listed.
Electrical Rough-In2/14/20202/14/20202/14/2020PPASS
DetailsMark Moncarr
3rd floor units ; 1st floor south maintenance closet. Phone #: ###-#### Inspection requested via web by Kevin Burke Ok cover 3rd floor.
Electrical Rough-In2/13/20202/14/20202/14/2020ACANC
DetailsMark Moncarr
3rd floor units, 1st floor south Mechanical room Phone #: ###-#### >> Inspection requested via web by Kevin Burke Inspection cancelled from web by: Kevin Burke
Conference2/5/20202/5/20202/5/2020PDONE
DetailsMark Moncarr
Conference Phone #: ###-#### Inspection requested via web by Kevin Burke Discussed not having recept in hallway that is under 10' in length, and recept within peninsula footprint covers all of the peninsula even if a sink or something similar is in place. 24" requirement is not used.
Electrical Rough-In2/3/20202/3/20202/3/2020PPASS
DetailsEric Story
1st ; 2nd Units only Phone #: ###-#### Inspection requested via web by Kevin Burke
1st and 2nd floors-units ok to cover
Conference12/18/201912/18/201912/18/2019PDONE
DetailsMark Moncarr
Low volt panels Phone #: ###-#### Inspection requested via web by Kevin Burke Talked to contractor about Media panel location and clearences. Will have approximately 26". Ok to locate panels in areas requested. Only work that would need to be done would be to replace a 110v recept if needed.
Electrical Rough-In10/3/201910/3/201910/3/2019APASS
DetailsMark Moncarr
Under slab ground work. Phone #: ###-#### Inspection requested via web by Kevin Burke Ok cover grd work from center to W side of slab.
Electrical Rough-In10/2/201910/2/201910/3/2019PPASS
DetailsMark Moncarr
Under slab Phone #: ###-#### Inspection requested via web by Kevin Burke Ok cover grd work on center to E side of slab
Electrical Rough-In9/12/20199/13/20199/13/2019APASS
DetailsMark Moncarr
Ground works through stairwell stem wall. Phone #: ###-#### Inspection requested via web by Kevin Burke Ok cover conduit S side of building.
Electrical Rough-In8/21/20198/21/20198/21/2019PPASS
DetailsMark Moncarr
Ufer in footing to run up stem wall and CMU wall Phone #: ###-#### Inspection requested via web by Kevin Burke Ok cover ufer. 20ft #4 cu