Information based on query as of Thursday, July 4, 2024.
Permit Information
Permit NumberELE19-04031
StatusFinaled
Name TRI STATE ELECTRIC
Site Address 802 W BANNOCK ST Unit: 308
Project Name 
Customer Number 
ePlanReviewNo
Description
Alteration: Suite 308 (3rd floor) for the Bank of Jackson Hole Tenant improvement
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final12/11/201912/12/201912/12/2019APASS
DetailsRock A. Hudson
CONTACT NAME ROB LAWRENCE Phone #: ###-#### Inspection requested via web by Deb Gooden
No card posted. Final ok
Final12/10/201912/11/201912/11/2019ANR
DetailsRock A. Hudson
Contact: Rob Lawrence Phone #: ###-#### Inspection requested via web by Deb Gooden
2 Receptacles on coffee bar not working, switched power feeding an emergency/ exit. Will recall when ready
Electrical Rough-In12/5/201912/5/201912/5/2019PPASS
DetailsRock A. Hudson
Contact: Rob Lawrence ceiling inspection please Phone #: ###-#### Inspection requested via web by Deb Gooden
Print stated no fire walls or protection requred.
Grid rough in ok cover
Electrical Rough-In12/4/201912/5/201912/5/2019ACANC
DetailsRock A. Hudson
Contact: Rob Lawrence. ceiling inspection please Phone #: ###-#### >> Inspection requested via web by Deb Gooden Inspection cancelled from web by: Deb Gooden
Electrical Rough-In10/18/201910/21/201910/21/2019PPASS
DetailsRock A. Hudson
Contact: Rob Lawrence Phone #: ###-#### Inspection requested via web by Deb Gooden
Discussed the existing conduits and raceways exposed during remodel that are not up to todays code. If existing are not used as part of this remodel and there are not life safety issuesthey are ok to remain as originally installed. If used in any way they shall conform to today code.
BCC 4-05-32- Code violations not to be retained. 110.26- Work clearance shall be provided for HVAC disconnect for electric furnace located in a small enclosed space large enough for unit only and disconnect located above unit with 480 volt circuit present.
Coffee bar walls only rough in ok cover