Permanent Service | 10/28/2019 | 10/28/2019 | 10/28/2019 | A | PASS |
Mark Moncarr
|
|
|
1 grd rod added, bonding verified and other corrections made. ps o/h rec ok
|
Permanent Service | 10/18/2019 | 10/21/2019 | 10/21/2019 | A | FAIL |