Information based on query as of Sunday, June 23, 2024.
Permit Information
Permit NumberELE19-04181
StatusFinaled
Name BEACON ELECTRIC
Site Address 10792 W FRANKLIN RD
Project Name 
Customer Number 
ePlanReviewNo
Description
Alteration: electrical for replacing duct heaters for VAV, new RTU and remodel with new wall on 2nd floor data room, upgrading lights in data room
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final6/22/20206/22/20206/22/2020APASS
DetailsTom Saunders
Please call so I can meet you. Thanks Phone #: ###-#### Inspection requested via web by Ron Zimmerman...

new hallway grid...ok to cover
job complete...ok to final
card signed
Electrical Rough-In5/6/20205/6/20205/6/2020PPASS
DetailsRock A. Hudson
for ceilings upstairs except one room. Please call when your on your way as I am about 15 minutes away. Thanks Phone #: ###-#### Inspection requested via web by Ron Zimmerman
Level 2 misc rooms except "Scada" rm grid rough in ok cover
Electrical Rough-In5/1/20205/1/20205/1/2020PPASS
DetailsTom Saunders
reinspect ceiling on 1st floor. Call me when you arrive to let you in.
Thanks,
Ron Phone #: ###-#### Inspection requested via web by Ron Zimmerman...1st floor grid complete...ok to cover
Electrical Rough-In4/26/20204/27/20204/27/2020APASS
DetailsTom Saunders
Give me a call when you arrive. I will be on site
thanks,
Ron Phone #: ###-#### Inspection requested via web by Ron Zimmerman...
new ceiling grid...several areas ok to cover...areas given on tag...E hallway, men's bath, breakroom, electrical rm office, locker room, front entry...
Electrical Rough-In4/27/20204/27/20204/27/2020AFAIL
DetailsTom Saunders
Give me a call when you arrive. I will be on site
thanks,
Ron Phone #: ###-#### Inspection requested via web by Ron Zimmerman...

correction notice given
1) all data cabling, fire alarm wiring, and any low voltage wiring will be support and not laying on grid
2) S/O cord being used as permanent wiring shall be removed...S/O not rated for permanent wiring or used above grid
Electrical Rough-In10/30/201910/31/201910/31/2019APASS
DetailsTom Saunders
rough in for new wall on 2nd floor data room Phone #: ###-#### Inspection requested via web by Ron Zimmerman...ok to cover