Permit Information
Permit NumberELE19-04394
StatusFinaled
Name PERRINE ELECTRIC
Site Address 4935 N QUAIL SUMMIT PL
Project Name 
Customer Number 
ePlanReviewNo
Description
Complete Installation (includes room count and per: new home
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final7/8/20207/9/20207/9/2020PPASS
DetailsMark Moncarr
Phone #: ###-#### Inspection requested via web by danny perrine Ok final
Permanent Service12/13/201912/16/201912/16/2019ACANC
DetailsMark Moncarr
wrong inspection- Tom Phone #: ###-####
Rough-In Permanent Service11/22/201911/25/201911/25/2019APASS
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by danny perrine
Rough in ok cover p/s u/g n ok
Rough-In Permanent Service11/21/201911/22/201911/22/2019AFAIL
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by danny perrine
110.3- Recessed can covers shall be installed tightly to junction boxes. North garage mud room, north spare bed.
250.64(D)(1)- Grounding electrode conductor shall have an external tap and extend to each service disconnect,
250.148- Metal boxes shall be connected to an equipment grounding conductor.
300.4- Nail plates needed in south garage marked with X.
300.15- NM cables shall terminate in a box. Recess can in utility make up missed.
334.12- NM cables shall not be installed where subject to damage. North garage HRs cut corner due to drywall nailer missing.