Final | 5/11/2020 | 5/12/2020 | 5/12/2020 | A | PASS |
James Ady
|
|
|
Phone #: ###-#### Inspection requested via web by Heath Thomas Final ok
|
Electrical Rough-In | 12/16/2019 | 12/16/2019 | 12/16/2019 | P | PASS |
Rock A. Hudson
|
|
|
Code on side entry door is (8098 lock) Phone #: ###-#### Inspection requested via web by Heath Thomas Rough in ok cover
|
Electrical Rough-In | 12/13/2019 | 12/13/2019 | 12/13/2019 | P | FAIL |
Rock A. Hudson
|
|
|
Code on side entry door is (8098 lock) Phone #: ###-#### Inspection requested via web by Heath Thomas 110.3- Recessed can junction box covers shall be completely installed, entry and bedroom. 300.4- Nail plates needed in family room marked with X. 334.30- Secure NM cable with in 12" of boxes, batroom and master vanity receptacles. * Missed wiring can in bathroom. * Secure meter base cover.
|