Final | 1/2/2020 | 1/2/2020 | 1/2/2020 | A | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Ron Zimmerman Final ok
|
Final | 12/30/2019 | 12/31/2019 | 12/31/2019 | A | FAIL |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Ron Zimmerman 210.8(B)- All receptacle outlets located with in 6' of a sink shall have GFCI protection. Breakroom. 300.15- All cables shall terminate in a box. above grid just in from door. 314.25- All boxes shall have covers. Above grid just in from door.
|
Electrical Rough-In | 12/11/2019 | 12/11/2019 | 12/11/2019 | P | PASS |
Eric Story
|
|
|
Phone #: ###-#### Inspection requested via web by Ron Zimmerman Walls only ok to cover
|