Permit Information
Permit NumberELE20-00297
StatusFinaled
Name HIGH GROUND ELECTRIC & CONSTRUCTION
Site Address 3256 E EASTGATE DR
Project Name 
Customer Number1242020
ePlanReviewNo
Description
Alteration or Repair: Rough in basement. Rough in kitchen upstairs remodel
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final3/11/20203/11/20203/11/2020PPASS
DetailsJames Ady
Corrections are complete Phone #: ###-#### Inspection requested via web by Kendra Lanham corrections made final ok
Final3/10/20203/10/20203/10/2020PFAIL
DetailsJames Ady
House is not occupied and key is on top of the meter base. Phone #: ###-#### Inspection requested via web by Kendra Lanham 210.8A6 Kitchen counter receps shall be GFCI protected. 422.31 Hood and Dishwasher need Disc./lockouts. 408.4 Circuit directory needed for garage panel. 110.3 Dead recep stair way half wall, Down laundry room, Bulbs beeded for Bath vanity and down front bed lights.
Electrical Rough-In1/27/20201/28/20201/28/2020APASS
DetailsJames Ady
Re-inspect rough in Phone #: ###-#### Inspection requested via web by Kendra Lanham Up kitchen and full basement ok to cover
Electrical Rough-In1/24/20201/27/20201/27/2020PNR
DetailsJames Ady
Basement framing - electrical rough - in
Kitchen upstairs - relocate outlets on wall Phone #: ###-#### Inspection requested via web by Kendra Lanham Recep needs added in Down hall as per 210.52H. Need to add smoke detectors. Basement is open and an open path exists to attic. Basement panel needs stuffed and abandoned wire removed Re-call when finished.