Permit Information
Permit NumberELE20-00311
StatusFinaled
Name COMMERCIAL ELECTRIC INC
Site Address 100 N 8TH ST
Project Name 
Customer NumberCEI 763
ePlanReviewNo
Description
Alteration: Provide electrical services that comply with and satisfy all requirements on approved drawings and plans.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final6/9/20206/10/20206/10/2020APASS
DetailsRock A. Hudson
The requested GFCI breakers have been installed and facility is now ready for final inspection. Phone #: ###-#### Inspection requested via web by Joe McLean Final ok
Final6/8/20206/9/20206/9/2020PFAIL
DetailsRock A. Hudson
Facility is ready for final inspection. Please contact Jeff with any questions or concerns. ###-#### Phone #: ###-#### Inspection requested via web by Joe McLean 210.8(B)- All receptacles 3 phase up to 100 amp and single phase up to 50 amp located in kitchen areas shall have GFCI protection. Esspresso and oven.
Conference5/26/20205/26/20205/26/2020PFAIL
DetailsRock A. Hudson
We need to confer with inspector prior to installing owner supplied lighting fixtures. Please call Jeff ###-####. Phone #: ###-#### Inspection requested via web by Joe McLean Looked at luminaires and all packaging, unable to locate a listing accepted by the US.
110.3(B)- All electrical equipment shall be tested and approved by an acceptable testing company. These luminaires are not to be installed unless field evaluated and approved prior to installation. Photos of packaging and instructions taken.
Electrical Rough-In4/27/20204/28/20204/28/2020APASS
DetailsRock A. Hudson
There were 4 window receptacles installed that need to be inspected prior to cover. Please contact Jeff with any questions. ###-####. Phone #: ###-#### Inspection requested via web by Joe McLean
Access shall be provided for junction boxes above hardlid. Along south wall 1 center of west window and 1 for next widow to east.
Hardlids rough in ok cover.
Electrical Rough-In4/24/20204/27/20204/27/2020APASS
DetailsRock A. Hudson
In need of a rough-in inspection prior to cover. Please call Brenden with any issues. ###-#### Phone #: ###-#### Inspection requested via web by Joe McLean
Show window receptacles and circuits not included on print, will be required as per 210.62. Wall rough in only ok cover
Electrical Rough-In4/17/20204/17/20204/17/2020PPASS
DetailsRock A. Hudson
There was some additional underground installation that needs to be inspected. Please call Jeff with any questions at ###-####. Phone #: ###-#### Inspection requested via web by Joe McLean
Called and informed the violation of
240.24(E)- Overcurrent devices shall not be located in a bathroom. Offered a solution of creating a seperation by enclosing panel behind a door but to be careful to make sure all required work space is present at time of final as per 110.26.
Underground extension rough in ok cover.
Electrical Rough-In3/25/20203/26/20203/26/2020PPASS
DetailsEric Story
The underground electrical conduits need inspected prior to pouring concrete. Please call Jeff ###-#### with any questions or issues. Phone #: ###-#### Inspection requested via web by Joe McLean
Approved plans on-site
U/G ok to cover