Final | 5/12/2020 | 5/12/2020 | 5/12/2020 | P | PASS |
James Ady
|
|
|
Reinspect service clearance for final Phone #: ###-#### Inspection requested via web by Robert Schroder (Fencing was removed at time of inspection) Corrections made Final ok
|
Final | 5/11/2020 | 5/11/2020 | 5/11/2020 | P | FAIL |
James Ady
|
|
|
Late afternoon please, key in front receptacle box Phone #: ###-#### Inspection requested via web by Robert Schroder 110.26A1. Depth of work space shall be 36in. (26in from fence to Service)
|
Rough-In Permanent Service | 3/12/2020 | 3/12/2020 | 3/12/2020 | A | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Robert Schroder Rough in ok cover p/s u/g n ok
|
Electrical Rough-In | 1/28/2020 | 1/28/2020 | 1/28/2020 | A | PASS |
Eric Story
|
|
|
inspect underground conduit for cover Phone #: ###-#### Inspection requested via web by Robert Schroder U/G ok to cover from garage to house ok to cover
|