Permit Information
Permit NumberELE20-00601
StatusFinaled
Name CAIN CHAD ROBERT
Site Address 2010 S LONGMONT AVE
Project Name 
Customer Number 
ePlanReviewNo
Description
Homeowner Online - Complete Installation (includes: Completeing indoor lights and outlets throughout the ADU. Outdoor full service was done by qualified electrician.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final5/26/20205/27/20205/27/2020APASS
DetailsRock A. Hudson
Shea *screened* Phone #: ###-#### Final ok
Final5/20/20205/21/20205/21/2020PFAIL
DetailsRock A. Hudson
Shay *screened* Phone #: ###-####
210.8(A)- All receptacle outlets installed in garage and outdoor locations shall have GFCI protection.
314.20- All boxes positioned 1/4" or more fron surface of wall shall have spark rings installed. forgot to list on correction but did inform verbally.
314.42- NM cable shall be protected from damage when entering a metal enclosure. Minisplit disconnect.
406.9(A)- Receptacle outlets located in damp or wet locations shall be WR type. Outdoor receptacles not protected from weather shall have in-use covers installed, west side and deck. 406.12(1)- All receptacle outlets required by 210.52 shall be tamper resistant type.
Conference3/3/20203/6/20203/6/2020APASS
DetailsJames Ady
Shea Phone #: ###-#### Discussed verious make up items and when next inspection should be scheduled.
Electrical Rough-In3/6/20203/6/20203/6/2020APASS
DetailsJames Ady
Shea Phone #: ###-#### ADU And garage rough in ok
Conference2/20/20202/21/20202/21/2020APASS
DetailsJames Ady
shea Phone #: ###-#### Discussed alot of info. Required circuits for dwelling unit, wire size AFCI protection, GFCI protection, wall spacing, counter spacing. owner has hand out