Final | 8/4/2020 | 8/4/2020 | 8/4/2020 | P | PASS |
Daryl DeGrange
|
|
|
Screened-Tyler Phone #: ###-#### corrections complete, final ok
|
Final | 8/3/2020 | 8/4/2020 | 8/4/2020 | A | FAIL |
Daryl DeGrange
|
|
|
ok with video/photo // Tyler Phone #: ###-#### NEC 406.9 Receptacles shall not be installed within or directly over a bathtub or shower stall. NEC 300.5 Underground installations, conduit or other raceways shall be installed to meet the minimum cover requirement of 12 in. for 120 volt GFCI protected. 6in. minimum cover for 30 volts or less
|
Final | 8/3/2020 | 8/3/2020 | 8/3/2020 | P | FAIL |
Daryl DeGrange
|
|
|
Not living in home // Tyler Phone #: ###-#### NEC 210.8(A)(2) All 120 volt, single phase, 15 and 20 amp receptacles installed garages shall be GFCI portected, outlet near furnace. NEC 210.8(A)(3) All120 volt, single phase, 15 and 20 amp receptacles installed outdoors shall be GFCI protected, front porch. NEC 406.12 All 15 and 20 ampere 120 and 250 volt nonlocking-type receptacles in dwelling units require Tamper Resistanted Receptacles. NEC 352.30(A) PVC conduit shall be securely fastened within 3 ft. service meter base.
|
Conference | 7/13/2020 | 7/13/2020 | 7/13/2020 | P | PASS |
Tom Saunders
|
|
|
new build .. SCREENED // Tyler Phone #: ###-####...discussed wiring of island receptacles...1 per island to meet requirement
|
Electrical Rough-In | 4/9/2020 | 4/10/2020 | 4/10/2020 | A | CANC |
Tom Saunders
|
|
|
screened // Tyler Phone #: ###-####...needed rough perm service...scheduled and resulted
|
Rough-In Permanent Service | 4/10/2020 | 4/10/2020 | 4/10/2020 | A | PASS |
Tom Saunders
|
|
|
screened // Tyler Phone #: ###-####... rough in ok to cover p/s u/g new ok
|
Electrical Rough-In | 4/8/2020 | 4/8/2020 | 4/8/2020 | P | CANC |
Tom Saunders
|
|
|
Tyler **Cleared** Phone #: ###-####...not ready...needed conference
|
Conference | 4/8/2020 | 4/8/2020 | 4/8/2020 | P | PASS |
Tom Saunders
|
|
|
Tyler **Cleared** Phone #: ###-####... discussed, make up of outlet and switches, GFCI requirement for all receptacles in bathrooms, powering of SD, dining rm circuit requirement, expansion joint at service required to be expanded halfway, 8/3 at panel needs proper connector-not B/A glued to coupling-needs positive crimp on wire, recessed can lighting junction boxes installed at first location of all rooms with recessed can lighting, hot tub wiring completed to exterior both ends
|
Conference | 3/2/2020 | 3/2/2020 | 3/2/2020 | P | DONE |
Mark Moncarr
|
|
|
Discussed service requirements and layout of house. Dedicated circuits. wall spacing etc. Homeowner has a grasp on what he is doing. Call me Tom with any questions.
|
Final | 3/2/2020 | 3/2/2020 | 3/2/2020 | P | CANC |
Mark Moncarr
|
|
|
Tyler Phone #: ###-#### Changed to a conference.
|