Information based on query as of Friday, June 28, 2024.
Permit Information
Permit NumberELE20-00750
StatusVoid/No Violation
Name TRAX ELECTRIC
Site Address 974 N MAPLE GROVE RD
Project Name 
Customer Number15794
ePlanReviewNo
Description
New: New electrical and lighting for 974 Maple Grove, BLDG 10
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Electrical Rough-In6/9/20206/10/20206/10/2020APASS
DetailsTom Saunders
underground for bollard lights
late morning if you can Tom Phone #: ###-#### Inspection requested via web by Todd Hall...feeds ok to cover...GFCI protected circuit in PVC
Electrical Rough-In6/9/20206/9/20206/9/2020PNR
DetailsTom Saunders
underground inspection for bollard light conduits Phone #: ###-#### Inspection requested via web by Todd Hall...not ready
Electrical Rough-In6/3/20206/3/20206/3/2020PPASS
DetailsTom Saunders
pole base inspection Phone #: ###-#### Inspection requested via web by Todd Hall...
ok to pour
Electrical Rough-In5/27/20205/28/20205/28/2020APASS
DetailsTom Saunders
inspection for carport power riser conduits Phone #: ###-#### Inspection requested via web by Todd Hall...ok to cover
Electrical Rough-In4/29/20204/29/20204/29/2020PPASS
DetailsTom Saunders
ceiling drops Phone #: ###-#### Inspection requested via web by Todd Hall...corrected..ok to cover
Electrical Rough-In4/28/20204/29/20204/29/2020AFAIL
DetailsTom Saunders
ceiling drops bldg 10 Phone #: ###-#### Inspection requested via web by Todd Hall....
1) NMB/Romex shall be strapped and supported by staples or approved means...334.30
2)NMB/romex shall be protected a minimum 1/4" from face of material...taping to T channel not acceptable means
Rough-In Permanent Service4/6/20204/7/20204/7/2020APASS
DetailsTom Saunders
building 10 (12 plex)
all units if possible Phone #: ###-#### Inspection requested via web by Todd Hall...
12 units ok to cover
p/s u/g new ok...13 meters
Electrical Rough-In3/11/20203/11/20203/11/2020PPASS
DetailsTom Saunders
Todd Phone #: ###-####...breezeway ceilings ok to cover
Electrical Rough-In3/3/20203/3/20203/3/2020PPASS
DetailsMark Moncarr
breezeways and West wall for cover of panel feeders.
Please call Todd to discuss previous underground inspection Phone #: ###-#### Inspection requested via web by Todd Hall Ok cover breezeway all floors and 1st floor W wall for feeders.