Final | 4/2/2020 | 4/2/2020 | 4/2/2020 | P | PASS |
Tom Saunders
|
|
|
Phone #: ###-#### Inspection requested via web by Ryan Wilson...120V circuits...GFCI protection...ok to final
|
Permanent Service | 4/1/2020 | 4/1/2020 | 4/1/2020 | P | PASS |
Tom Saunders
|
|
|
Phone #: ###-#### Inspection requested via web by Ryan Wilson...corrections made...
p/s o/h ok to connect...meter installed
|
Permanent Service | 3/30/2020 | 3/31/2020 | 3/31/2020 | A | FAIL |
Mark Moncarr
|
|
|
Phone #: ###-#### Inspection requested via web by Ryan Wilson
1. Not a listed irreversible crimp.
|
Electrical Rough-In | 3/16/2020 | 3/16/2020 | 3/16/2020 | P | PASS |
Rock A. Hudson
|
|
|
Food truck in Albertsons parking lot Phone #: ###-#### Inspection requested via web by Ryan Wilson 250.64(C)- Grounding electrode conductor shall be continuous. Set screw butt-splice located on farside of side walk. Interior of food shack rough in ok cover.
|
Rough-In Permanent Service | 3/10/2020 | 3/10/2020 | 3/10/2020 | P | FAIL |
Mark Moncarr
|
|
|
Please inspect Korean food truck building in parking lot. Thanks Phone #: ###-#### Inspection requested via web by Ryan Wilson 1. Available Fault Current needed. 2. GEC needs physical protection, also is a trip hazard on public sidewalk. 3. Guy kit needed for masts over 30" as per IDP. Posted notice on window.
|
Temporary Service | 3/9/2020 | 3/9/2020 | 3/9/2020 | P | CANC |
Rock A. Hudson
|
|
|
Mariela - Temporary service panel for food truck on corner of five mile and Ustick. If questions call permit desk "Gabe" Phone #: ###-#### Needed permenant service and food shack rough in inspection, see rough in/ ps
|
Rough-In Permanent Service | 3/9/2020 | 3/9/2020 | 3/9/2020 | P | FAIL |
Rock A. Hudson
|
|
|
Mariela - Temporary service panel for food truck on corner of five mile and Ustick. If questions call permit desk "Gabe" Phone #: ###-#### 230.62- Energized parts shall be guarded from accidental contact. Unable to locate panel cover. Not installed when I arrived. 334.12- NM cable shall not be installed in a wet location. Interior of a conduit installed in a wet location is a wet location.
|
Electrical Rough-In | 3/5/2020 | 3/5/2020 | 3/5/2020 | A | FAIL |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Ryan Wilson Store manager helped locate area to coolers located between deli and back south west corner of store, no discription of work performed, No Building permit attached to electrical permit. Stamped set of prints on site, no access to area above to verify disconnecting means, listings confirmed with cooler assembly. Must attach to building permit, must meet on site and provide access to disconnecting means above coolers as noted on print.
|