Information based on query as of Saturday, April 27, 2024.
Permit Information
Permit NumberELE20-01251
StatusIssued
Name DUAL VOLTAGE ELECTRICAL LLC
Site Address 3567 E VIA ESTANCIA LN
Project Name 
Customer Number20160
ePlanReviewNo
Description
Alteration: New electrical Service for Subdivision Irrigation Pump Station on the corner of E Via Estancia Lane and S Via Privada Ln
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Permanent Service4/8/20204/9/20204/9/2020APASS
DetailsJames Ady
New Electrical Service for Subdivision Irrigation pump station on the corner of S Via Privada Ln and E Via Estancia Ln Phone #: ###-#### Inspection requested via web by Kotton Corder 358.42 Couplings and connectors used with EMT shall be made up tight. Could loosen raintight fittings with fingers. Tighten all fittings. Corrections shall be made prior to final. Fault current under 3500A Shall be posted at final p/s u/g n ok