Permit NumberELE20-01516
StatusIssued
Name SOLAR CASCADE
Site Address 316 N BROOKDALE DR
Project Name 
Customer Number 
ePlanReviewNo
Description
Alteration or Repair: Upgrading Electrical panel, and wiring through house
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Electrical Rough-In7/29/20207/29/20207/29/2020PPASS
DetailsJames Ady
3480 code Phone #: ###-#### Inspection requested via web by Dave Brueggemann Contractor adding wire for back w/p by a/c at time of rough in. corrections made rough in ok
Electrical Rough-In7/28/20207/28/20207/28/2020PFAIL
DetailsJames Ady
Door code 3480 Phone #: ###-#### Inspection requested via web by Dave Brueggemann corrections not made
Electrical Rough-In7/24/20207/24/20207/24/2020AFAIL
DetailsJames Ady
Code 3480 Phone #: ###-#### Inspection requested via web by Dave Brueggemann 300.15. All wire shall terminate in a box.( Any abandoned, accessible Rag wire shall be removed or terminated in box) 300.4 Nail plates needed in kitchen back spalsh and under living room window. 210.52 Recep need added L&R of master slider and R of living room slider and Dining room wall. 210.70A2. All exits shall have wall controlled exterior lighting.210.52E3 All decks and patios shall have receps. Range and A/C wire need terminated in panel. Please install panel cover or protective front durring construction. Mech room needs light and recep before final
Permanent Service5/5/20205/5/20205/5/2020PCANC
DetailsJames Ady
Door code 3480 Phone #: ###-#### Inspection requested via web by Dave Brueggemann called in twice
Permanent Service5/5/20205/5/20205/5/2020PPASS
DetailsJames Ady
Door code 3480 Phone #: ###-#### Inspection requested via web by Dave Brueggemann p/s o/h rec ok
Permanent Service5/3/20205/4/20205/4/2020AFAIL
DetailsJames Ady
Phone #: ###-#### Inspection requested via web by Dave Brueggemann 250.92A1 & A2. Metal raceways containing Service entrance shall be Bonded, Metal enclosures shall be bonded. 200.6B Nuetral conductor shall be identified. 334.30 NM cable shall be supported within 12in of box