Permit Information
Permit NumberELE20-01518
StatusIssued
Name TREASURE VALLEY ELECTRIC INC
Site Address 311 N ELM AVE
Project Name 
Customer Number 
ePlanReviewNo
Description
Addition: Electrical in new building
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Permanent Service7/28/20207/28/20207/28/2020PPASS
DetailsJames Ady
Phone #: ###-#### Inspection requested via web by Steve Craig As per 445, rough in inspections ok with BLD on hold. No final until BLD is in issued status. p/s o/h n ok
Permanent Service7/27/20207/27/20207/27/2020PFAIL
DetailsEric Story
Phone #: ###-#### Inspection requested via web by Steve Craig
110.24 AFC calc required proir to service being energized
Electrical Rough-In7/7/20207/8/20207/8/2020ACANC
DetailsJames Ady
Ceiling inspection for recessed cans. Phone #: ###-#### Inspection requested via web by Steve Craig No answer from contractor. No visable resessed cans needing covered. hardlids throughout.
Electrical Rough-In5/6/20205/7/20205/7/2020APASS
DetailsRock A. Hudson
Elelctrical rough-in of new construction. Phone #: ###-#### Inspection requested via web by Steve Craig Rough in ok cover
Electrical Rough-In5/5/20205/5/20205/5/2020PFAIL
DetailsRock A. Hudson
Rough in inspection at new Roosevelt Market Phone #: ###-#### Inspection requested via web by Steve Craig
300.22(B)- MC cable shall not be installed in air handling spaces.
314.20- MC cables shall terminate in a box.
330.30- MC cables shall be secured by approved means with in 12" of a box.
City approved set of prints on site