INSP-Final Inspection | 5/14/2001 | 5/14/2001 | 5/14/2001 | P | PASS |
Rick Jackson
|
|
|
Added by Inspector: 409 On 5/14/2001 3:29:48 PM
|
INSP-Final Inspection | 5/4/2001 | 5/7/2001 | 5/7/2001 | A | PART |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 05/04/2001 at 09:40:50. Contact: ###-####. dry system test at 59 seconds; need to test alarms 5/7/2001 11:13:13 AM
|
INSP-Final Inspection | 5/3/2001 | 5/3/2001 | 5/3/2001 | P | PART |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 05/03/2001 at 08:41:54. Contact: ###-####. okay on aerosol racking 5/3/2001 2:49:07 PM
|
INSP-Final Inspection | 4/26/2001 | 4/27/2001 | 4/27/2001 | P | CANC |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 04/26/2001 at 12:38:05. Contact: ###-####.
|
INSP-Final Inspection | 4/9/2001 | 4/11/2001 | 4/11/2001 | P | FAIL |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 04/09/2001 at 15:26:19. Contact: ###-####. dry sprinkler system took 72 seconds; inspector test in wrong location 4/11/2001 6:12:17 PM
|
INSP-Sprinkler Rough-in/Hydro | 3/14/2001 | 3/15/2001 | 3/15/2001 | A | PART |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 03/14/2001 at 15:22:22. Contact: ###-####. hydro on all wet systems okay 3/15/2001 1:16:21 PM
|
INSP-Sprinkler Rough-in/Hydro | 3/13/2001 | 3/14/2001 | 3/14/2001 | A | FAIL |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 03/13/2001 at 08:31:16. Contact: ###-####. c/n issued 3/14/2001 11:33:06 AM
|
INSP-Sprinkler Rough-in/Hydro | 2/19/2001 | 2/20/2001 | 2/20/2001 | A | FAIL |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 02/19/2001 at 08:30:50. Contact: ###-####. c/n issued - earthquaking; FDC location; clearance at base of riser; dry and rack systems not approved 2/21/2001 10:33:44 AM
|