Permit Information
Permit NumberFIR00-00630
StatusFinaled
Name COMMERCIAL FIRE PROTECTION
Site Address 1276 W RIVER ST
Project NameSPR RIVER PLAZA
Customer Number 
ePlanReview 
Description
TO FIRE SPRINKLER A NEW 3-STORY, WOOD FRAMED, TYPE V ONE-HOUR, 26,851 ft/2, SHELL AND CORE OFFICE BUILDING. THE FIRST FLOOR IS APPROXIMATELY 8,987 FT/2 THE SECOND FLOOR IS APPROXIMATELY 9,054 FT/2 THE THIRD FLOOR IS APPROXIMATELY 8,810 FT/2. THE INSTALLATION OF THE FIRE SPRINKLER SYSTEM IS USED TO SUBSTITUTE FOR THE ONE-HOUR FIRE-RESISTIVE CONSTRUCTION. ALL WORK PER THE APPROVED PLANS, ATTACHED COMMENT LIST, THE 1997 EDITION OF THE UFC, BOISE CITY ORDINANCE, FIRE DEPARTMENT APPROVAL AND INSTALLED PER RELATED ADOPTED PAMPHLETS. FOUNDATION PERMIT IS BLD99-2056. THIS PERMIT IS FOR THE SHELL ONLY. THE SECOND AND THIRD FLOORS MUST HAVE THE CORRIDOR FINISHED TO PROVIDE ACCESS TO THE SECOND MEANS OF REQUIRED EGRESS. THIS REQUIREMENT MUST BE FINISHED AT THE TIME OF THE FIRST OCCUPANT. UNDERGROUND FIRE LINE WAS PERMITTED UNDER FIR00-00025. BLD99-02394 (SHELL), FUTURE T.I.'S BLD00-02397 (3RD FLOOR) AND BLD00-02507 (2ND FLOOR), DRH99-0067. This permit is attached to the shell permit.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Conference8/14/20018/14/20018/14/2001PPASS
DetailsRick Jackson
Added by Inspector: 409 On 8/14/2001 4:12:44 PM
INSP-Final Inspection1/9/20011/9/20011/9/2001APASS
DetailsRick Jackson
Scheduled by Inspector: 409 On 1/9/2001 8:57:26 AM
INSP-Final Inspection1/9/20011/8/20011/8/2001AFAIL
DetailsRick Jackson
Scheduled by Inspector: 409 On 1/9/2001 9:00:09 AM dry air pressure not working; valve not supervised; check valve needs repair kit; standard response head in elevator machine room 1/9/2001 9:02:43 AM
INSP-Final Inspection12/29/200012/29/20001/2/2001PFAIL
DetailsRick Jackson
Scheduled by a contractor via Hello! on 12/29/2000 at 09:08:04. Contact: ###-####. outside control valve; hydro dry and FDC; tampers on dry system 1/2/2001 10:06:20 AM
INSP-Supply line flush12/27/200012/28/200012/28/2000ANR
DetailsRick Jackson
Scheduled by a contractor via Hello! on 12/27/2000 at 11:45:08. Contact: ###-####.
INSP-Supply line flush12/26/200012/27/200012/27/2000APASS
DetailsRick Jackson
Scheduled by a contractor via Hello! on 12/26/2000 at 13:40:07. Contact: ###-####./// flush okay 12/27/2000 4:17:09 PM
INSP-Supply line flush12/15/200012/15/200012/15/2000PPART
DetailsRick Jackson
Scheduled by a contractor via Hello! on 12/15/2000 at 09:35:03. Contact: ###-####.///// underground hydro only okay 12/15/2000 4:04:47 PM
INSP-Sprinkler Rough-in/Hydro12/8/200012/11/200012/11/2000PFAIL
DetailsRick Jackson
Scheduled by a contractor via Hello! on 12/08/2000 at 09:31:17. Contact: ###-####./// hydro okay on attic system. need additional sway bracing; overspaced heads; painted heads; inspectors test not installed per plans and will relocate 12/12/2000 9:41:21 AM