Permit Information
Permit NumberFIR01-00021
StatusFinaled
Name NORTHWEST SALES COMPANY
Site Address 200 W FRONT ST
Project NameCOURTHOUSE-ALM
Customer Number 
ePlanReviewNo
Description
Ada County Courthouse - To install an automatic and manual fire alarm system throught the complex. Alarm plans relate to TI permit BLD00-01649 as welll as shell permit BLD99-03383. System coverage will include smoke detection in I3 areas, complete manual system (required by the I3 and A2.1), a/v annunciation, elevator recall, smoke detection for damper and door holdopen release and HVAC shutdown, sprinkler system monitoring. Some tenant areas are not included in these plans, which will be required to have separate Fire Alarm Permits inconjuction with the TI permits.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection12/28/200112/28/200112/28/2001APASS
DetailsRick Jackson
Added by Inspector: 409 On 12/28/2001 9:42:30 AM
INSP-Alarm Testing12/21/200112/21/200112/21/2001AFAIL
DetailsRick Jackson
Scheduled by Inspector: 409 On 12/21/2001 4:32:44 AM preaction system not working; c/n issued for ther items 12/24/2001 5:54:14 AM
INSP-Alarm Testing12/20/200112/20/200112/20/2001AFAIL
DetailsRick Jackson
Scheduled by Inspector: 409 On 12/20/2001 6:20:07 AM need to complete basement alarm testing 12/21/2001 4:33:16 AM
INSP-Alarm Testing12/19/200112/19/200112/19/2001AFAIL
DetailsRick Jackson
Scheduled by Inspector: 409 On 12/19/2001 11:36:36 AM not finished testing 12/20/2001 6:20:49 AM
INSP-Alarm Testing12/17/200112/18/200112/18/2001AFAIL
DetailsRick Jackson
Scheduled by Inspector: 409 On 12/17/2001 4:48:55 PM some horns not working; identified on plans; not complete with the install 12/19/2001 11:37:18 AM
INSP-Alarm Testing12/17/200112/17/200112/17/2001PFAIL
DetailsRick Jackson
Scheduled by a contractor via Hello! on 12/17/2001 at 10:03:55. Contact: ###-####. wlak through of second and third floor for horn/strobe locations: items marked on approve plans, will continue on 12/18 12/17/2001 5:00:09 PM
INSP-Alarm Testing12/7/200112/7/200112/7/2001AFAIL
DetailsRick Jackson
Scheduled by Inspector: 409 On 12/7/2001 5:58:53 AM completed first floor alarms; c/n issued 12/7/2001 3:28:52 PM
INSP-Alarm Testing12/5/200112/6/200112/6/2001PFAIL
DetailsRick Jackson
###-#### david started testing the first floor; sprinklers not monitored; strobes in corridors over 15 ft from ends; detectors at door hold opens in wronglocation 12/7/2001 6:01:04 AM
FIR-Aging Inspection10/15/200110/15/200110/15/2001 NR
DetailsRick Jackson
wip 10/15/2001 7:27:35 AM