INSP-Final Inspection | 6/6/2001 | 6/6/2001 | 6/6/2001 | P | PASS |
Rick Jackson
|
|
|
Added by Inspector: 409 On 6/6/2001 2:35:09 PM
|
INSP-Sprinkler Rough-in/Hydro | 5/1/2001 | 5/2/2001 | 5/2/2001 | A | PART |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 05/01/2001 at 14:24:52. Contact: ###-####. need FDC location adjusted to maintain 3 foot clearance; above and underground hydro okay 5/2/2001 10:20:56 AM
|
INSP-Sprinkler Rough-in/Hydro | 4/23/2001 | 4/24/2001 | 4/24/2001 | A | FAIL |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 04/23/2001 at 13:08:12. Contact: ###-####. high temp heads at heaters; standard response head in elevator machine room; earthquaking needed in several areas as noted on plans; review notes indicate 155 temp heads - need designer input 4/24/2001 9:34:52 AM
|
INSP-Supply line flush | 4/24/2001 | 4/24/2001 | 4/24/2001 | A | PASS |
Rick Jackson
|
|
|
Added by Inspector: 409 On 4/24/2001 9:33:20 AM
|
INSP-Supply line flush | 4/23/2001 | 4/24/2001 | 4/23/2001 | A | PART |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 04/23/2001 at 11:40:12. Contact: ###-####. cover inspection - okay to cover 4/23/2001 2:00:57 PM
|
INSP-Supply line flush | 4/18/2001 | 4/19/2001 | 4/18/2001 | A | CANC |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 04/18/2001 at 08:35:25. Contact: ###-####. Disp set to [CANC] by a contractor via Hello! on 04/18/2001 at 13:13:46.
|
INSP-Conference | 3/6/2001 | 3/6/2001 | 3/6/2001 | P | PART |
Rick Jackson
|
|
|
Paul ###-#### called contractor and he wanted to know if he could rock some hallways as the sprinkler piping will still be viewable - rocking approved 3/6/2001 3:37:48 PM
|