Permit Information
Permit NumberFIR01-00314
StatusFinaled
Name GRINNELL FIRE PROTECTION
Site Address 101 N COLE RD
Project NameSPR FURNITURE ROW
Customer Number 
ePlanReview 
Description
*FURNITURE ROW* To install fire sprinkler system, which includes fire pump, jocky pump, in-rack protection and 8" ductile iron underground supply into an existing remodeled one story, 27,662 ft/2, Type VN Unlimited area structure, referred to "OAK EXPRESS", and a 27,296 ft/2, one story, Type VN Unlimited area, called "DENVER MATTRESS" & "SOFA MART." These facilities require full fire sprinkler protection for unlimited area. (The intended uses in the building is for three Group M Occupancy tenants). No separate underground permit issued. These systems, installation, materials design and coverage, etc. shall meet all requirements and related code items and issues which include, but not be limited to the 1997 UFC 1003, 8102, 8103, 8104, NFPA 13-1999, 20-1999, 24-1995, 72-1999 and the BCO, as regulated by the Fire Department. This permit is attached to a shell permit: BLD01-00220.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection11/9/200111/9/200111/9/2001PPASS
DetailsTroy Cobbley
Added by Inspector: 430 On 11/9/2001 6:33:22 PM Fire alarm system finaled. OK for perm occ.
INSP-Final Inspection11/7/200111/8/200111/8/2001PPASS
DetailsTroy Cobbley
Fire sprinkler system finaled. OK for perm occ 11/9/2001 3:31:20 PM
INSP-Final Inspection11/1/200111/2/200111/2/2001PFAIL
DetailsTroy Cobbley
Contractor did not have approvals on new rack storage heights and east antifreeze loop failed hydro 11/2/2001 4:47:26 PM
INSP-Sprinkler Rough-in10/18/200110/18/200110/18/2001PPART
DetailsTroy Cobbley
left c/n. Oak express max stor. is 15'. Top shelf is now at 15'. no storage allowed on top shelf. EQ bracing is con. to bottom and mid chord. prove it will work or move to top chord. 10/18/2001 11:21:52 AM
INSP-Sprinkler Rough-in/Hydro10/16/200110/16/200110/16/2001PPART
DetailsTroy Cobbley
Hydro on Sofa mart, denver mattress and overhead supply line OK. Rough-in on sofa mart and denver mattress OK but see c/n, 10/16/2001 12:48:43 PM
INSP-Sprinkler Rough-in/Hydro9/28/200110/5/200110/5/2001ACANC
DetailsJoe Tawney
###-#### MIKE
INSP-Sprinkler Rough-in/Hydro9/26/200110/4/200110/4/2001PPART
DetailsJoe Tawney
Oak Express hydro OK. Fire pump test OK 10/4/2001 5:36:45 PM
INSP-Sprinkler Rough-in/Hydro9/26/200110/4/200110/4/2001PCANC
DetailsJoe Tawney
Cancel double entry 10/3/2001 8:13:07 AM
INSP-Final Inspection9/17/20019/18/20019/18/2001PPART
DetailsJoe Tawney
OK on supply line flush and Ok on underground hydro test 9/18/2001 4:04:27 PM
INSP-Supply line flush8/15/20018/16/20018/16/2001APART
DetailsJoe Tawney
OK to cover supply line 8/16/2001 11:18:00 AM
INSP-Sprinkler Rough-in7/11/20017/11/20017/11/2001PPART
DetailsJoe Tawney
OK to cover small rooms in SE corner of bldg 7/11/2001 3:48:43 PM