INSP-Final Inspection | 6/26/2003 | 6/27/2003 | 6/27/2003 | A | PASS |
Troy Cobbley
|
|
|
KEVIN; Phone #: ###-#### Internet Inspection Request from: Darla Downs
|
INSP-Conference | 5/2/2003 | 5/2/2003 | 5/2/2003 | A | PART |
Rick Jackson
|
|
|
met with Kevin while performing an inspection for the racking permit (BLD02-02472); the racking was signed by me as all the items were corrected (door hardware/flue space/storage height); I searched the database and found this permit for the alarm system as Steve Keuter had called previously about this permit; I told Keven to get ADT to call for a final inspection as the last inspection was back in 2002 by Troy; he said he would contact ADT to schedule the inspection
|
INSP-Final Inspection | 10/18/2002 | 10/22/2002 | 10/22/2002 | P | FAIL |
Troy Cobbley
|
|
|
batteries in the aux. power supply are not supervized. Provide map at the FACP 10/22/2002 2:50:34 PM
|
INSP-Final Inspection | 12/12/2001 | 12/13/2001 | 12/13/2001 | P | FAIL |
Troy Cobbley
|
|
|
provide additional D113 module for battery supervision and test batteries, adjust tamper switch on gate valve to give steady signal, provide tamper switch on alarm valve trim, adjust flow switch so alarm comes in under 90 seconds, provide map of system at fire alarm panel, provide NFPA 72 forms 12/13/2001 12:38:35 PM
|
FIR-Aging Inspection | 10/29/2001 | 10/29/2001 | 10/29/2001 | | NH |
Troy Cobbley
|
|
|
Visited job site system is in. I notified contractor that inspection is needed. 10/29/2001 4:04:50 PM
|