Permit Number | FIR01-00348 |
Status | Expired |
Name |
GRINNELL FIRE PROTECTION
|
Site Address |
3511 S TK AVE
|
Project Name | SPR BIG O TIRES-COLUMNS |
Customer Number | |
ePlanReview | |
Description |
*BIG "O" TIRE* To modifiy/relocate 48 existing (required) column sprinklers on the adjacent side of the same columns to prevent possible damage. NFPA 13:7-9.8.2 COLUMNS WITHIN RUBBER TIRE STORAGE - Where fireproofing is not provided, steel columns shall be protected as follows:
(1) Storage exceeding 15 ft through 20 ft in height — one sidewall sprinkler directed to one side of the column at a 15-ft level.
(2) Storage exceeding 20 ft in height — two sidewall sprinklers, one at the top of the column and the other at a 15-ft level, both directed to the side of the column. All work per NFPA 13 and UFC requirements as regulated by the Fire Department. Permit is not attached to any existing permit. No plans or notes attached. (This is the notes) *JWA*
|