Permit NumberFIR01-00350
StatusFinaled
Name DEBEST FIRE PROTECTION
Site Address 8049 W EMERALD ST
Project NameSPR BOISE TOWN PLZA A&B
Customer Number 
ePlanReview 
Description
SHOPS AT BOISE TOWNE PLAZA - BUILDING A-B (SHELL) - TO FIRE SPRINKLER TO ORDINARY GROUP 2 HAZARD (AT 120' FT/2 SPACING-MERCHANTILE) A NEW 18,000 FT/2, ONE STORY RETAIL SHELL BUILDING. BUILDING "A" IS 8,280 FT/2, BUILDING "B" IS 9,720 FT/2. THIS BUILDING IS CONSTRUCTED OF MASONRY EXTERIOR WALLS WITH A WOOD FRAME ROOF SYSTEM. THIS BUILDING WILL BE FULLY FIRE SPRINKLERED. THE SPRINKLERS ARE BEING USED FOR ALLOWABLE AREA INCREASE. THIS PERMIT IS FOR A SHELL BUILDING ONLY. NO OCCUPANCY IS ALLOWED UNDER THIS PERMIT. SEPARATE TENANT IMPROVEMENT PERMITS WILL BE REQUIRED TO FINISH THIS BUILDING FOR OCCUPANCY. ALL INSTALLATION PER THE APPROVED PLANS, ATTACHED COMMENT LIST, UFC, AND RELATED AND ADOPTED NFPA PAMPHLETS . THIS PERMIT IS PERMIT IS ATTACHED TO (SHELL) PERMIT BLD00-02631. UNDERGROUND PERMIT IS UNDER FIR01-00285. *JWA*
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection10/26/200110/26/200110/26/2001APASS
DetailsTroy Cobbley
Added by Inspector: 430 On 10/26/2001 8:07:48 AM Shell sprinkler system OK for sign off
INSP-Sprinkler Rough-in/Hydro9/28/200110/1/200110/1/2001PPART
DetailsJoe Tawney
Rough-in OK. Above ground hydro OK. Eq brace to be added in two locations. One upright to be added at mech. Check coverage at draft stops during TI 10/1/2001 4:36:02 PM
INSP-Supply line flush9/5/20019/5/20019/5/2001 PART
DetailsJoe Tawney
Ok on underground hydro test. Need copy of test certificate 9/5/2001 4:38:26 PM