INSP-Final Inspection | 12/17/2002 | 12/18/2002 | 12/18/2002 | P | PASS |
Troy Cobbley
|
|
|
fire alarm finaled 12/18/2002 1:51:53 PM
|
INSP-Alarm Testing | 12/16/2002 | 12/17/2002 | 12/17/2002 | A | FAIL |
Troy Cobbley
|
|
|
separate the low air signals from the tamper switches signals, provide key and map for the knox box 12/17/2002 2:52:46 PM
|
INSP-Alarm Testing | 12/7/2001 | 12/10/2001 | 12/10/2001 | A | CANC |
Troy Cobbley
|
|
|
duplicate inspection 12/10/2001 4:13:07 PM
|
INSP-Final Inspection | 12/7/2001 | 12/7/2001 | 12/7/2001 | P | FAIL |
Troy Cobbley
|
|
|
Added by Inspector: 430 On 12/7/2001 3:35:45 PM Provide tamper switches on control valves in riser room, provide tamper switch on dry pipe alarm trim, provide "Fire Sprinkler Room" sign on riser room, hard wire the air compressor, provide lock on fire alarm panel circuit, provide "knox box", provide map in knox box and at facp, provide low air pressure switch, verify single pressure switch is ok for two dry pipe risers, test exterior bell and sign
|