Permit Information
Permit NumberFIR01-00435
StatusFinaled
Name ST LUKES 98228
Site Address 190 E BANNOCK ST
Project NameALM-ST LUKES-EAST TOWER
Customer Number 
ePlanReview 
Description
ST LUKES-EAST TOWER EXPANSION - To install six new fire alarm control extender panels to provide manual and automatic fire alarm protection within the new addition TI areas on the 1st and 2nd floors and for the unfinished shell areas. The alarm system design indicates sprinkler monitoring, elevator recall, total area smoke detection on the 1st and 2nd floors (which plans indicate are to be used for release of smoke dampers by floor of origin in these areas), induct detectors for smoke damper release in unfinished building areas, duct detectors for HVAC air handler shutdown, and a previously approved method of a/v annunciation, all connected to the existing FS-90+ system now in service for the SLRMC. There will also be related modifications to the existing FACP-30 panel located in the Maintenance Boiler Room.
This permit does not include the Nurse call system.
The building permit (BLD01-00234) is to perform Tenant Improvement Construction of a 19,315 sq. ft. 1st floor for a new Emergency Department (ED) and 21,205 sq. ft. on the 2nd floor for Neonatal Intensive Care Unit (NICU). Construction to be of non-combustible framing with fire-resistive sheetrock covering to create 1-hour rated exit corridors, reception, lobbies & waiting areas; sleeping, exam, & treatment rooms; support area for associated staff and equipment; to install suspended ceiling grid system; electrical, mechanical & plumbing systems to satisfy adopted city, state & federal requirements for this occupancy group; to divide patient sleeping & treatment areas into suites with 1-hour occupancy separation per code, each with required exit access systems to serve their particular area without exiting through another. Note : This building is fully fire sprinklered as a condition of the "I" occupancy classification.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection3/7/20023/7/20023/7/2002APASS
DetailsRick Jackson
Added by Inspector: 409 On 3/7/2002 10:16:31 AM
INSP-Alarm Testing2/21/20022/22/20022/22/2002AFAIL
DetailsRick Jackson
Scheduled by Inspector: 409 On 2/21/2002 12:42:12 PM fail; need standpipe control valve supervised; tampers on antifreeze loop not working; all dampers tested and working except exhaust dampers on 4th floor shafts; in duct detectors installed at dampers in sub basement; need copy of record of completion 2/22/2002 2:24:01 PM
INSP-Alarm Testing2/20/20022/21/20022/21/2002AFAIL
DetailsRick Jackson
Scheduled by Inspector: 409 On 2/20/2002 12:16:40 PM in-duct detectors required at return air dampers in sub basement; first floor programming problems - need to retest; ground and basement alarms okay 2/21/2002 12:43:34 PM
INSP-Alarm Testing2/19/20022/20/20022/20/2002AFAIL
DetailsRick Jackson
Scheduled by Inspector: 409 On 2/19/2002 4:24:35 PM smokes in bathrooms on second floor to heat detectors; some dampers not closing 2/20/2002 11:42:06 AM
INSP-Alarm Testing2/19/20022/19/20022/19/2002PFAIL
DetailsRick Jackson
Added by Inspector: 409 On 2/19/2002 4:24:10 PM 4th floor NAC not reporting batery loss trouble; need detectors at 4th floor exhaust dampers
INSP-Alarm Testing2/15/20022/15/20022/15/2002AFAIL
DetailsRick Jackson
Scheduled by Inspector: 409 On 2/15/2002 12:33:58 PM tested all sprinkler control and tampers - okay; tested 4th floor and extender panel will not report trouble with battery loss; need to test dampers on 4th; no audibles on all floors 2/15/2002 12:37:46 PM
FIR-Aging Inspection2/1/20022/1/20022/1/2002 NR
DetailsRick Jackson
wip 2/1/2002 9:37:08 AM
FIR-Aging Inspection1/18/20021/18/20021/18/2002 NR
DetailsRick Jackson
wip 1/18/2002 11:59:48 AM