Permit Information
Permit NumberFIR01-00436
StatusFinaled
Name SIMPLEX/GRINNELL
Site Address 746 W MAIN ST
Project NameALM-CAPITAL TERRACE
Customer Number 
ePlanReview 
Description
SCOPE: To upgrade the existing Capital Terrace building alarm system in accordance with a letter by Larry Hansen dated 1/24/2002 and the terms as noted in the approval dated 2/11/02 by the Boise City Fire Department, and in an e-mail memo by Larry Hansen dated 2/4/2002 and the terms as noted in the approval dated 2/11/02 by Sam Rogers. This is Phase 1 of the approved upgrade agreement. Per the agreement, additional manual pull stations (to provide pulls at all exits) and upgrading a/v alarm devices to meet UFC 1007.3.3.3 and NFPA 72, will not be required under this Phase 1 permit.


The associated building permit (BLD 00-02971, PITA PIT) is to remodel for a new 1,011 sq.ft. tenant (784 sq.ft. main floor, 227 sq. ft. mechanical mezzanine) in existing building, changing occupancy from an (A 3) restaurant to a (B) occupancy restaurant per approved plans on file. The former restaurant space is being split up into two tenant spaces. Adjacent portion is "McDonalds" done under BLD00 01146. Work to include miscellaneous demolition, upgrading a restroom to meet current accessibility standards, one hour rated CMU wall infill in existing one hour rated occupancy separation wall, interior finish, new walk in cooler, fire sprinkler adjustments, mechanical equipment including a new Ventless Hood installation over electric griddle, mechanical work, plumbing work, and electrical work.

2/26/2004 - ADDITIONAL SCOPE: The architectural backgrounds do not reflect the field conditions of current tenants. (i.e. Scandiadown, AMG Fine Housewares, Clark Photography, Boise Floral Company and Purple Sage are no longer there). Napoleon's for Men, 110 N. 8th, BLD03-01106 is a TI that has occurred since 1/1/2003. Per the agreement, effective 1/1/2003, any TI will trigger the upgrade of the existing manual fire alarm system and existing audio/visual (speaker/strobes) throughout the building. A new Fire Alarm Permit will be required for the completion of the upgrade agreement dated 2/4/2002.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection2/23/20052/24/20052/24/2005APASS
DetailsTroy Cobbley
Fire alarm finaled 2/24/2005 9:29:08 AM
INSP-Final Inspection9/14/20049/15/20049/15/2004AFAIL
DetailsRick Jackson
bryan; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles Need updated, rated door on shaft and resubmittals 9/15/2004 10:08:10 AM
INSP-Final Inspection8/20/20048/23/20048/23/2004PFAIL
DetailsRick Jackson
brian; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles Need plan modifications due to deletions/additions; need rated doors at access holes in top of shaft to maintain 2 hr shaft; need mechanical engineering analysis for Gino's TI and plans to match changes 8/23/2004 4:21:32 PM
INSP-Final Inspection8/18/20048/19/20048/19/2004PPART
DetailsTroy Cobbley
BRAIN; Phone #: ###-#### Internet Inspection Request from: Annette Moore

Completed elevator testing on North and South elevators; acceptable per the drawings.

Completed sprinkler testing on fire pump, Dry System A and Dry System B; acceptable per the drawings.

Left to test:

All existing kitchen hoods (less Gino's Pizzeria and Creapery).
Center elevator, controls being installed on Friday 8/20/2004.
HVAC shutdown system for Gino's Pizzeria.
INSP-Final Inspection8/10/20048/13/20048/13/2004PFAIL
DetailsRick Jackson
BRIAN; Phone #: ###-#### Internet Inspection Request from: Annette Moore See notes from Mary F. 8/13/2004 4:37:42 PM
INSP-Conference7/13/20047/13/20047/13/2004PPART
DetailsRick Jackson
brian - note:capital terrace parking garage; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles Met with Brian and smoke detectors are required at top of the shaft in each beam pocket 7/13/2004 4:04:27 PM
INSP-Conference4/5/20044/6/20044/6/2004APART
DetailsRick Jackson
robert; Phone #: ###-#### Internet Inspection Request from: Darla Downs Met with Robert about the scope of this permit; Larry H. has approved the addition of the hood systems to the alarm panel and the connection of the alarm panels but has not approved any other work; I need a conference with Sam and Mary about the scope of work of this permit 4/6/2004 11:21:39 AM