Permit Number | FIR01-00498 |
Status | Expired |
Name |
COMMERCIAL FIRE PROTECTION
|
Site Address |
131 N MILWAUKEE ST
|
Project Name | SPR TOYS 'R' US UPGRADE, ETC |
Customer Number | |
ePlanReview | |
Description |
*Toys ‘R' Us* The verification/upgrade and conformance of an existing retail facility, meeting the minimum requirements of UFC Article 81 for "High-Piled Combustible Storage". Includes the upgrade the existing roof/ceiling sprinkler water demand to meet minimum requirements of NFPA 13: 7-4.4.3.1, incorporating figure 7-4.4.2.3(b), interpolated with 7-4.4.2.3(a), for the storage commodity class IV, storage/display height of 13'-6", with a: .39 gpm density over 2000 ft/2 minimum, at the most remote area. To modify sprinkler spacing at or below the maximum protection area spacing allowed per NFPA 13:5-6.2.2 for "High-Piled/Rack" storage, (100 ft/2). This permit is not attached to a building permit. It was created a Fire Department, verifying UFC requirements. All construction, fire sprinkler work and related issues shall be per the UFC, adopted NFPA pamphlets and BCO requirements, as regulated by the Fire Department.
|