INSP-Alarm Testing | 3/22/2002 | 3/25/2002 | 3/25/2002 | A | PASS |
Troy Cobbley
|
|
|
fire alarm system finaled 3/25/2002 11:03:58 AM
|
INSP-Final Inspection | 3/6/2002 | 3/8/2002 | 3/8/2002 | A | CANC |
Troy Cobbley
|
|
|
cancelled by the contractor 3/8/2002 10:40:39 AM
|
FIR-Aging Inspection | 2/1/2002 | 2/1/2002 | 2/1/2002 | | NR |
Troy Cobbley
|
|
|
work in progress 2/1/2002 11:51:57 AM
|
INSP-Final Inspection | 1/17/2002 | 1/18/2002 | 1/18/2002 | A | FAIL |
Troy Cobbley
|
|
|
Contractor needs to resubmit showing substitution of spot detectors for duct detectors in "Mens Warehouse", HVAC unit in "Billiards and BarStools" does not shut down, provide map of device locations and addresses at the FACP 1/18/2002 11:48:31 AM
|
INSP-Conference | 12/3/2001 | 12/3/2001 | 12/3/2001 | P | DONE |
Troy Cobbley
|
|
|
Contractor wanted alternate location for remote annunciator. I referred it to Sam Rogers 12/4/2001 11:28:48 AM
|