INSP-Final Inspection | 11/26/2002 | 11/27/2002 | 11/27/2002 | A | PASS |
Rick Jackson
|
|
|
forest says its not finaled yet ###-#### trip test of all dry systems completed; all under a minute 11/27/2002 2:09:42 PM
|
INSP-Alarm Testing | 9/26/2002 | 9/27/2002 | 9/27/2002 | A | NR |
Rick Jackson
|
|
|
###-#### willreschedule for next week; need additional personnel to test 9/27/2002 10:11:34 AM
|
INSP-Sprinkler Rough-in/Hydro | 9/20/2002 | 9/23/2002 | 9/23/2002 | P | PART |
Rick Jackson
|
|
|
###-#### hydro okay on the five systems; still need to trip test 9/23/2002 3:40:02 PM
|
INSP-Final Inspection | 9/11/2002 | 9/13/2002 | 9/13/2002 | P | FAIL |
Rick Jackson
|
|
|
###-#### attempted hydro on all systems; numerous leaks; will try again next week 9/16/2002 8:34:35 AM
|
INSP-Final Inspection | 1/9/2002 | 1/10/2002 | 1/10/2002 | A | FAIL |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 01/09/2002 at 15:05:57. Contact: ###-####. all tampers/flows, etc tested okay. need to add head in small room in basement and additional drain 1/10/2002 12:06:58 PM
|
INSP-Sprinkler Rough-in/Hydro | 1/3/2002 | 1/4/2002 | 1/4/2002 | P | PART |
Rick Jackson
|
|
|
Scheduled by Inspector: 409 On 1/3/2002 2:41:40 PM last riser passed 24 hour air test 1/4/2002 3:02:34 PM
|
INSP-Sprinkler Rough-in/Hydro | 1/3/2002 | 1/3/2002 | 1/3/2002 | P | PART |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 01/03/2002 at 10:48:01. Contact: ###-####. start of 24 hr test of last system on riser 4 1/3/2002 2:46:35 PM
|
INSP-Sprinkler Rough-in/Hydro | 12/27/2001 | 12/28/2001 | 12/28/2001 | A | PART |
Rick Jackson
|
|
|
Scheduled by Inspector: 409 On 12/27/2001 1:06:04 PM all air test complete except the system for floor two 12/28/2001 9:02:39 AM
|
INSP-Sprinkler Rough-in/Hydro | 12/26/2001 | 12/26/2001 | 12/27/2001 | P | FAIL |
Rick Jackson
|
|
|
###-#### slope of mains on south side on all floors not sloped back to east sides; air test started at 8:00 am for three risers on west wall of riser room - will return on 11/28 at 8 am 12/27/2001 1:08:29 PM
|
INSP-Sprinkler Rough-in | 12/11/2001 | 12/11/2001 | 12/11/2001 | P | FAIL |
Rick Jackson
|
|
|
###-#### need comments for approved plans; plans on site but no comments - couldn't locate comments 12/12/2001 4:59:05 AM
|