Permit Information
Permit NumberFIR01-00514
StatusFinaled
Name RAY/JAN WEED
Site Address 2360 W SPRING MOUNTAIN DR
Project NameSPR WEED RESIDENCE
Customer Number 
ePlanReview 
Description
To install a NFPA 13D fire sprinkler system in a 2172 ft/2 single story, single family dwelling with a 1280 ft/2 finished daylight basement. This lot is within a hillside area and must meet the requirements of the hillside ordinances. Class "A" roof and 30 ft. defensible area will be required. Driveway must meet the UFC weight capacity, be paved 12 ft. wide and have adequate turnaround. This house will be equipped with a NFPA 13D automatic sprinkler system. The sprinkler flow alarm shall be attached to the residence smoke detection system. The sprinkler flow alarm shall be attached to the residence smoke detection system. All fire sprinkler work and related (which includes dual service water supply, backflow prevention (provided by others), shall be per approved plans, engineering/red-lining and attached review notes, all as regulated by the Fire Department. This permit is attached to: BLD01-00662. (JWA)
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection5/2/20025/2/20025/2/2002PPASS
DetailsRick Jackson
Added by Inspector: 409 On 5/2/2002 2:45:03 PM
INSP-Final Inspection5/1/20025/1/20025/1/2002PFAIL
DetailsTroy Cobbley
secure the power supply to outlet for alarms and lock valves on riser and backflow preventer
INSP-Final Inspection3/20/20023/21/20023/21/2002AFAIL
DetailsRick Jackson
JIM ###-#### FOR ACCESS exposed CPVC in riser/mechanical room. GC will get with TVFP and provide clarification; appears not to meet listing of Blazemaster 3/21/2002 9:14:13 AM
INSP-Sprinkler Rough-in11/14/200111/15/200111/15/2001APASS
DetailsTroy Cobbley
OK for cover up 11/15/2001 2:21:25 PM
INSP-Sprinkler Rough-in10/22/200110/22/200110/22/2001PPASS
DetailsTroy Cobbley
Rough-in OK. Tenting inspec. needs to be done. Install head beneath stairs. 10/24/2001 8:24:51 AM