Permit NumberFIR01-00521
StatusFinaled
Name SHILO AUTOMATIC SPRINKLER CO
Site Address 10185 W EMERALD ST
Project NameSPR EMERALD TECH BLDG. E
Customer Number 
ePlanReview 
Description
EMERALD TECH CENTER BUILDING "E" (SHELL) - TO INSTALL A COMPLETE ORDINARY GROUP 2 HAZARD FIRE SPRINKLER SYSTEM WHICH INCLUDES A 6" C-900 UNDERGROUND SUPPLY IN A NEW 15,000 FT/2, ONE STORY, SHELL BUILDING. THE BUILDING IS CONSTRUCTED OF CONCRETE TILT-UP EXTERIOR WALLS WITH INTERIOR STEEL STRUCTURAL COLUMNS, STEEL ROOF JOISTS WITH METAL ROOF DECK AND SINGLE PLY ROOFING SYSTEM. THIS IS A SHELL SPRINKLER PERMIT ONLY. NO OCCUPANCY IS ALLOWED UNDER THIS PERMIT. SEPARATE TENANT IMPROVEMENT PERMITS ARE REQUIRED TO FINISH EACH TENANT SPACE FOR OCCUPANCY. ALL CONSTRUCTION PER THE APPROVED PLANS, ATTACHED COMMENT LIST, UFC AND ADOPTED NFPA RELATED PAMPHLETS AS REGULATED BY THE FIRE DEPARTMENT. THIS PERMIT IS ATTACHE TO THE BUILDING SHELL PERMIT: BLD01-01054.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection3/28/20023/28/20023/28/2002PPASS
DetailsRick Jackson
Added by Inspector: 409 On 3/28/2002 5:23:09 PM
INSP-Sprinkler Rough-in11/19/200111/19/200111/19/2001APASS
DetailsTroy Cobbley
Added by Inspector: 430 On 11/19/2001 9:03:21 AM Sprinkler rough-in OK
INSP-Sprinkler Rough-in/Hydro11/19/200111/19/200111/19/2001APASS
DetailsTroy Cobbley
Added by Inspector: 430 On 11/19/2001 10:54:05 AM Above ground hydro test OK.
INSP-Supply line flush11/16/200111/19/200111/19/2001APASS
DetailsTroy Cobbley
Supply line flush OK. 11/19/2001 9:02:24 AM
INSP-Supply line flush10/19/200110/19/200110/19/2001PPASS
DetailsTroy Cobbley
OK to cover rest of underground line 10/19/2001 1:57:13 PM
INSP-Sprinkler Rough-in10/9/200110/9/200110/9/2001PPART
DetailsJoe Tawney
OK to cover 10' out only 10/10/2001 9:33:03 AM