Information based on query as of Thursday, July 18, 2024.
Permit Information
Permit NumberFIR02-00005
StatusFinaled
Name TREASURE VALLEY FIRE PROTECTION
Site Address 3201 W AIRPORT WAY
Project NameSPR AIRPORT-NEW TERMINAL
Customer Number 
ePlanReview 
Description
*BOISE AIRPORT PASSENGER TERMINAL BUILDING-OVERHEAD* TO INSTALL COMPLETE FIRE SPRINKLER SYSTEMS WITH FIRE BOOSTER PUMP IN A NEW 311,820 FT/2, THREE STORY AIRPORT PASSENGER TERMINAL BUILDING FACILITY. BASEMENT CONSISTS OF 45,000 FT/2. THE NEW TERMINAL BUILDING WILL BE CONSTRUCTED OF CONCRETE AND STEEL STRUCTURAL FRAME. IT WILL BE FULLY FIRE SPRINKLERED. THIS TERMINAL BUILDING WILL REPLACE THE EXISTING TERMINAL BUILDING. THE PROJECT WILL BE CONSTRUCTED IN PHASES. SCHEDULE I, WILL BE CONSTRUCTED OUTSIDE OF THE EXISTING TERMINAL FOOTPRINT AND WILL INCLUDE THE BASEMENT SUPPORT AREAS, FIRST FLOOR BAGGAGE CLAIM/MAKE-UP, SECOND FLOOR TICKETING, ATO AND LEASE AREAS AND THE THIRD FLOOR ADMINISTRATIVE AND LEASE AREAS. SCHEDULE I ALSO INCLUDES CONSTRUCTION OF TEMPORARY ELEVATED WALKWAYS AND SECURITY CHECKPOINTS CONSTRUCTED OVER THE EXISTING TERMINAL BUILDING, TO CONNECT THE COMPLETED AND OPERATING SCHEDULE I BUILDING WITH THE EXISTING CONCOURSES. SCHEDULE II WILL INCLUDE DEMOLITION OF THE WEST END OF THE EXISTING TERMINAL BUILDING AND THE CONSTRUCTION OF THE FIRST FLOOR RENTAL CAR LOBBY AND GROUND LOAD LOBBY AND SECOND FLOOR SECURITY CHECKPOINT, FOOD COURT AREAS AND PASSENGER LINK TO EXISTING CONCOURSE 'B'. AFTER COMPLETION OF SCHEDULE II, THE REMAINDER OF THE EXISTING TERMINAL BUILDING, THE TEMPORARY ELEVATED WALKWAYS AND CONCOURSE 'A' WILL BE DEMOLISHED AND REMOVED. ALL CONSTRUCTION PER THE APPROVED PLANS AND ATTACHED COMMENT LIST. ALL RELATED WORK SHALL BE PER RED-LINED NOTES AND ATTACHED PLAN REVIEW COMMENTS AND CONDITIONS LIST AS REGULATED BY FIRE DEPARTMENT, WHICH COMPRISES AND BECOMES A PART OF THE APPROVED PLANS. A FIRE "INSPECTION CARD" IS REQUIRED AS A CONDITION OF THIS PERMIT, TO PROVIDE WITNESS COMPLIANCE WITH ADOPTED CODES & ORDINANCES. THIS FIRE PERMIT IS ATTACHED TO BUILDING PERMIT: BLD01-03428. UNDERGROUND FIRE PERMIT ISSUED PREVIOUSLY SUPPLYING THIS PERMITTED WORK IS: FIR01-00562.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection11/8/200411/8/200411/8/2004PPASS
DetailsRick Jackson
INSP-Final Inspection10/11/200410/11/200410/11/2004PFAIL
DetailsRick Jackson
brian; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles Dry system under walkway trip test okay; need straps on two hangers near stair; need air gauge at dry valve 10/11/2004 1:49:57 PM
INSP-Sprinkler Rough-in/Hydro10/6/200410/6/200410/6/2004PPART
DetailsRick Jackson
Scheduled by a contractor via Hello! on 10/6/2004 at 10:50:55 AM. Contact: ###-####. hydro on dry system under walkway okay 10/6/2004 12:59:01 PM
INSP-Sprinkler Rough-in/Hydro10/4/200410/5/200410/5/2004AFAIL
DetailsRick Jackson
Stop air test 43 psi Fail - air pressure at 38 psi 10/5/2004 11:44:21 AM
INSP-Sprinkler Rough-in/Hydro10/4/200410/4/200410/4/2004PDONE
DetailsRick Jackson
Start 24 hour test 12 pm with 43 psi on dry system under old walkway 10/4/2004 1:37:18 PM
INSP-Sprinkler Rough-in/Hydro9/17/20049/17/20049/17/2004PPART
DetailsRick Jackson
Scheduled by a contractor via Hello! on 9/17/2004 at 8:14:52 AM. Contact: ###-####. Okay in area D and E; the temp walkway dry system is not ready and will require all tests; the walkway sprinkler system must remain in service up until the demo time 9/17/2004 11:47:29 AM
INSP-Sprinkler Rough-in/Hydro9/15/20049/15/20049/15/2004PPART
DetailsRick Jackson
Scheduled by a contractor via Hello! on 9/15/2004 at 8:42:06 AM. Contact: ###-####. ^ inch main from pump room to concourse B hydro only okay 9/15/2004 2:35:24 PM
INSP-Sprinkler Rough-in/Hydro9/10/20049/10/20049/10/2004PPART
DetailsRick Jackson
Dry system for under terminal and walkway okay for hydro; 30 minutes to fill with air at 42 psi 9/10/2004 4:28:49 PM
INSP-Sprinkler Rough-in9/8/20049/8/20049/8/2004AFAIL
DetailsRick Jackson
Dry system air compressor takes over 30 minutes to fill system; need to trip dry system and set air compressor to come on above low air setting 9/8/2004 11:58:33 AM
INSP-Sprinkler Rough-in/Hydro9/3/20049/3/20049/3/2004PFAIL
DetailsRick Jackson
Scheduled by a contractor via Hello! on 9/3/2004 at 10:38:54 AM. Not holding pressure (second floor at SW corner) 9/3/2004 2:19:41 PM
INSP-Sprinkler Rough-in/Hydro8/31/20049/1/20049/1/2004APART
DetailsRick Jackson
Brian; 8:00 Hydro okay for east mechanical room, area D 1st floor and area E basement through 1st floor elevator area 9/1/2004 12:33:15 PM
INSP-Sprinkler Rough-in/Hydro8/30/20048/31/20048/31/2004ACANC
DetailsRick Jackson
Scheduled by a contractor via Hello! on 8/30/2004 at 2:49:20 PM. Contact: ###-####. Rescheduled by inspector for 9/1 8/31/2004 3:06:37 PM
INSP-Sprinkler Rough-in8/6/20048/6/20048/6/2004AFAIL
DetailsRick Jackson
Overspaced in roof mechanical room at grid F/5 - G/4 and 9-10 (only area checked) 8/6/2004 10:30:29 AM
INSP-Sprinkler Rough-in/Hydro8/5/20048/6/20048/6/2004APART
DetailsRick Jackson
Brian - ###-#### Hydro on west mechanical room on roof okay 8/6/2004 1:15:18 PM
INSP-Sprinkler Rough-in/Hydro8/4/20048/5/20048/5/2004PNR
DetailsRick Jackson
brian ; Phone #: ###-#### Internet Inspection Request from: Annette Moore Hydro not holding - rescheduled for 8/6 8/5/2004 2:09:39 PM
INSP-Sprinkler Rough-in/Hydro7/27/20047/27/20047/27/2004APART
DetailsRick Jackson
Area C hydro completed 7/27/2004 2:00:37 PM
INSP-Sprinkler Rough-in/Hydro7/23/20047/26/20047/26/2004PPART
DetailsRick Jackson
Brian; Phone #: ###-#### Internet Inspection Request from: Aimee Hughes Hydro on area C okay; EQ at (3-6 inch lines) expansion joint on second level okay 7/26/2004 2:58:31 PM
INSP-Sprinkler Rough-in6/8/20046/9/20046/10/2004APART
DetailsRick Jackson
###-#### brian okay to cover rotunda only; EQ needed at area by new walkway 6/10/2004 8:53:53 AM
INSP-Sprinkler Rough-in5/26/20045/26/20045/26/2004PPART
DetailsTroy Cobbley
Sprinkler pendants located in area "C" on the second floor west of the sky lights are ok to cover 5/26/2004 3:16:42 PM
INSP-Sprinkler Rough-in5/11/20045/12/20045/12/2004AFAIL
DetailsRick Jackson
Brian; Phone #: ###-#### Internet Inspection Request from: Aimee Hughes Need EQ on 4 inch on either side of skylight as they are overspaced 5/12/2004 11:26:04 AM
INSP-Sprinkler Rough-in4/19/20044/19/20044/19/2004PPART
DetailsRick Jackson
The 2.5 inch line in area D first floor has shifted from plans and branch lines installed per plans; need EQ at west end of 2.5 inch on first floor as it is overspaced from end of pipe; the tie-ins to exsisting mains aren't completed; okay on first floor area C and D - heads/drops not completed 4/19/2004 3:06:57 PM
INSP-Sprinkler Rough-in/Hydro6/3/20036/4/20036/4/2003PPART
DetailsRick Jackson
air test on three systems //// air tests okay; will need map updated to reflect current room numbers; system not left on and operational as it is not monitored by BOI personnel 6/4/2003 2:35:39 PM
INSP-Sprinkler Rough-in/Hydro6/3/20036/3/20036/3/2003PPART
DetailsRick Jackson
sam; Phone #: ###-#### Internet Inspection Request from: Barbara Moore started 24 hr test on three systems 6/3/2003 4:01:51 PM
INSP-Sprinkler Rough-in/Hydro5/28/20035/28/20035/28/2003PPASS
DetailsTroy Cobbley
sam; Phone #: ###-#### Hydro test for dry system area "B" is ok 5/28/2003 4:00:07 PM
INSP-Sprinkler Rough-in/Hydro5/23/20035/23/20035/23/2003PPART
DetailsRick Jackson
sam; Phone #: ###-#### Internet Inspection Request from: Barbara Moore tripped dry system to baggae handling area - trip time 1 minute; tampers and low air didn't report to fire panel; will need to reverify these signals for proper monitoring 5/23/2003 2:21:32 PM
INSP-Sprinkler Rough-in/Hydro5/7/20035/8/20035/8/2003APART
DetailsRick Jackson
hydro test on second floor area A and C; first floor area C; wet and preaction area B 5/8/2003 4:17:14 PM
INSP-Sprinkler Rough-in/Hydro4/10/20034/11/20034/11/2003PPART
DetailsRick Jackson
SAM ###-#### area A and C on third floor hydro okay 4/11/2003 3:44:29 PM
INSP-Sprinkler Rough-in/Hydro3/24/20033/25/20033/25/2003APART
DetailsRick Jackson
sam; Phone #: ###-#### Internet Inspection Request from: Annette Moore hydro okay on first floor Area A. 3/25/2003 10:11:08 AM
INSP-Sprinkler Rough-in3/11/20033/11/20033/11/2003PPART
DetailsRick Jackson
sam; Phone #: ###-#### Internet Inspection Request from: Annette Moore tested pump with TVFP and Russ of Nickerson 3/11/2003 4:30:02 PM
INSP-Sprinkler Rough-in/Hydro2/13/20032/14/20032/14/2003PPART
DetailsRick Jackson
sam; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie hydro okay on basement, feed mains and header in basement; preaction for computer room; future main feeds 2/14/2003 3:19:56 PM
INSP-Sprinkler Rough-in2/7/20032/7/20032/7/2003PPART
DetailsRick Jackson
###-#### okay to cover area between rotunda and ticket area; need fireproofing in spots 2/7/2003 2:17:17 PM
INSP-Sprinkler Rough-in/Hydro1/31/20031/31/20031/31/2003PPART
DetailsRick Jackson
Scheduled by a contractor via Hello! on 1/31/2003 at 9:26:33 AM. Contact: ###-####. will need heads in bottom of shaft on first floor' catwalk area okay 1/31/2003 3:12:22 PM
INSP-Sprinkler Rough-in1/10/20031/10/20031/10/2003AFAIL
DetailsRick Jackson
heads below 22 inches and numerous obstructed in Area A in catwalk area for baggage handling system
INSP-Sprinkler Rough-in/Hydro12/17/200212/17/200212/17/2002PPART
DetailsRick Jackson
SAM; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie antifreeze system and temp walkway areas are completed; hydro okay; tampers tested okay under FIR02-00480 12/18/2002 7:31:30 AM
INSP-Sprinkler Rough-in/Hydro12/13/200212/13/200212/13/2002PPART
DetailsRick Jackson
Phone #: ###-#### Internet Inspection Request from: Rita DeYoung hydro on temp walkway and r/i; will relocate heads at new wall as they are overspaced and at new room in temp wlakway 12/13/2002 4:06:19 PM
INSP-Sprinkler Rough-in/Hydro12/9/200212/9/200212/9/2002PPART
DetailsRick Jackson
###-#### 12/10/2002 10:45:25 AM r/i for temp walkway okay; hydro okay 12/10/2002 2:41:50 PM
INSP-Sprinkler Rough-in/Hydro12/2/200212/3/200212/3/2002APART
DetailsRick Jackson
Scheduled by a contractor via Hello! on 12/02/2002 at 13:21:53. Contact: ###-####. verified resubmittal on the skylight area; okay per plans; will need to verify that heads aren't painted 12/3/2002 11:35:16 AM
INSP-Sprinkler Rough-in10/11/200210/14/200210/14/2002APART
DetailsRick Jackson
area okay in concourse A for new bathroom 10/14/2002 9:25:27 AM
INSP-Final Inspection10/10/200210/11/200210/11/2002ACANC
DetailsRick Jackson
Scheduled by a contractor via Hello! on 10/10/2002 at 13:11:25. Contact: ###-####. rescheduled for 10/14 10/11/2002 4:46:19 PM
INSP-Sprinkler Rough-in9/26/20029/26/20029/26/2002PFAIL
DetailsRick Jackson
Phone #: ###-#### Internet Inspection Request from: Rita DeYoung control valves on 1st, 2nd and 3rd floors are located above ceiling; first floor area A is located within baggage conveyor area 9/26/2002 4:12:22 PM
INSP-Sprinkler Rough-in/Hydro9/4/20029/5/20029/5/2002AFAIL
DetailsRick Jackson
Scheduled by a contractor via Hello! on 09/04/2002 at 13:28:58. Contact: ###-####. heads obstructed/overspaced in basement mechanical; refer room; janitor room; EQ branch line in south room; add line and head in south room as shown on plans; heads painted in computer room; heads fire proofed in service corridor; temp walk way off concourse okay to cover; combustibles in concealed space by phone area; okay to cover mechanical chase on third floor 9/5/2002 11:05:16 AM
INSP-Sprinkler Rough-in/Hydro7/2/20027/3/20027/3/2002PFAIL
DetailsRick Jackson
SAM ###-#### heads obstructed in basement at west end mechanical; will continue r/i 7/3/2002 3:45:40 PM
INSP-Sprinkler Rough-in/Hydro7/1/20027/2/20027/2/2002ANR
DetailsRick Jackson
SAM ###-#### Sam didn't have the latest approved a job shack; talked to Greg on phone and they will have plans for pm inspection on 7/3/02 7/2/2002 3:52:43 PM
INSP-Sprinkler Rough-in1/14/20021/14/20021/14/2002PPART
DetailsRick Jackson
Added by Inspector: 409 On 1/14/2002 2:14:54 PM checked hangers in basement and retaining straps are installed where fireproofing is going to be applied this week.