Permit Information
Permit NumberFIR02-00038
StatusFinaled
Name NAGEL BEVERAGE CO
Site Address 5465 W IRVING ST
Project NameALM-NAGEL BEVERAGE CO
Customer Number 
ePlanReview 
Description
NAGEL BEVERAGE CO - To replace a fire alarm panel in an existing building. The new system will provide required offsite monitoring of the fire sprinkler system and include monitoring of existing duct smoke detectors for HVAC air handler shutdown. There is no associated building permit.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection6/21/20026/21/20026/21/2002APASS
DetailsTroy Cobbley
fire alarm finaled
INSP-Conference4/15/20024/15/20024/15/2002ADONE
DetailsTroy Cobbley
I spoke with Phil (###-####) and notified him that the existing elevator recall system will need to be intergrated with the new fire alarm system per NFPA 72 and that plans will need to be submitted for approval. The fire alarm panel as tested is operational
INSP-Conference4/9/20024/9/20024/9/2002PDONE
DetailsTroy Cobbley
I left the maintenance person (Jerry) a voice mail to make him aware of the existing elevator needing to be connected to the new fire alarm panel. I left him my cell phone number to contact me.
INSP-Alarm Testing4/4/20024/4/20024/4/2002PFAIL
DetailsTroy Cobbley
provide corrected zone map at facp panel, provide panel location map for knox box, provide current fire sprinkler riser inspection tag and flow test sprinkler system 1 to verify signal 4/5/2002 10:52:17 AM