Permit Number | FIR02-00070 |
Status | Finaled |
Name |
TREASURE VALLEY BIBILE CHURCH
|
Site Address |
12251 W USTICK RD
|
Project Name | TREASURE VALLEY BIBLE CHURCH |
Customer Number | |
ePlanReview | |
Description |
TREASURE VALLEY BIBLE CHURCH - To install a new fire alarm system in a new building. Plans for the alarm system include monitoring of the fire sprinkler system, induct smoke detectors for release of fire/smoke dampers, duct detectors for HVAC air handler shut down, area smoke detectors for release of fire/smoke door hold open devices, voice evacuation system in the Santuary , exit corridors and in the Chapel area which are A2.1 occupancies. The Gymnasium, which is also an A2.1, is to remain unfinished and unoccupied and will not be provided with voice evacuation until a separate fire alarm permit has been issued. One inside audible alarm with a manual pull station will be provided in the B occupancy portion of the building.
The associated building permit (BLD 01-02399) is to construct a new 30,522 sq. ft. one story, fully fire sprinklered church with classrooms, gym and offices. Building will have a two hour area separation wall with two types of construction. Gym and sanctuary will be Type II?1hr with remainder being Type V?1hr. Fire sprinklers shall be used for substitution of one?hour construction. One hour exit passageways shall be provided on each side of the sanctuary for the side exits.
|