Permit Information
Permit NumberFIR02-00070
StatusFinaled
Name TREASURE VALLEY BIBILE CHURCH
Site Address 12251 W USTICK RD
Project NameTREASURE VALLEY BIBLE CHURCH
Customer Number 
ePlanReview 
Description
TREASURE VALLEY BIBLE CHURCH - To install a new fire alarm system in a new building. Plans for the alarm system include monitoring of the fire sprinkler system, induct smoke detectors for release of fire/smoke dampers, duct detectors for HVAC air handler shut down, area smoke detectors for release of fire/smoke door hold open devices, voice evacuation system in the Santuary , exit corridors and in the Chapel area which are A2.1 occupancies. The Gymnasium, which is also an A2.1, is to remain unfinished and unoccupied and will not be provided with voice evacuation until a separate fire alarm permit has been issued. One inside audible alarm with a manual pull station will be provided in the B occupancy portion of the building.
The associated building permit (BLD 01-02399) is to construct a new 30,522 sq. ft. one story, fully fire sprinklered church with classrooms, gym and offices. Building will have a two hour area separation wall with two types of construction. Gym and sanctuary will be Type II?1hr with remainder being Type V?1hr. Fire sprinklers shall be used for substitution of one?hour construction. One hour exit passageways shall be provided on each side of the sanctuary for the side exits.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection9/25/20029/26/20029/26/2002APASS
DetailsTroy Cobbley
fire alarm finaled 9/26/2002 10:44:50 AM
INSP-Final Inspection9/24/20029/24/20029/24/2002PFAIL
DetailsRick Jackson
tested detectors for AHU shutsown - larger units have 30 second delay; need to trim back flange on weatherproof covers so the detector cover can be removed; need NFPA record of completion 9/24/2002 3:21:50 PM
INSP-Final Inspection9/18/20029/23/20029/23/2002PFAIL
DetailsTroy Cobbley
relocate the electric alarm bell to the fdc location, provide a dedicated non switched circuit for the air compressor, provide enclosures for the duct detectors. Test the dry pipe system for signals. 9/23/2002 3:31:47 PM 9/23/2002 3:37:39 PM