Permit Information
Permit NumberFIR02-00081
StatusFinaled
Name SHILO AUTOMATIC SPRINKLER CO
Site Address 356 W HALE ST
Project NameSPR BROOKSIDE APARTMENTS
Customer Number 
ePlanReview 
Description
Building C2 * To install a complete NFPA 13-1999 system in a new 19,077 ft/2 three story, wood framed, 18 unit apartment building, including the underground supply. NOTE: This building is fully fire sprinklered for one-hour substitution. Each floor is 6,359 ft/2 and contains 2 - two bedroom, two bath units and 2 - one bedroom, one bath units. The fire sprinkler system shall comply with NFPA 13-1999, red-lined plans, attached review comment and conditions list, as regulated by the Fire Chief. A fire "Inspection Card" is required as a condition of this permit, to provide witness of compliance with the same. This permit is attached to BLD01-0964.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection8/6/20028/7/20028/7/2002PPASS
DetailsRick Jackson
MIKE ###-####
INSP-Final Inspection7/31/20028/1/20028/1/2002ACANC
DetailsRick Jackson
Scheduled by a contractor via Hello! on 07/31/2002 at 11:20:22. Contact: ###-####. alarms not pretested by contractor 8/1/2002 9:05:34 AM
INSP-Sprinkler Rough-in/Hydro7/15/20027/17/20027/17/2002PPART
DetailsRick Jackson
Scheduled by a contractor via Hello! on 07/15/2002 at 11:35:54. Contact: ###-####. hydro okay on all systems 7/17/2002 12:52:21 PM
INSP-Supply line flush4/18/20024/19/20024/19/2002PPASS
DetailsRick Jackson
Scheduled by a contractor via Hello! on 04/18/2002 at 13:44:28. Contact: ###-####.
INSP-Sprinkler Rough-in/Hydro4/16/20024/16/20024/16/2002PPASS
DetailsRick Jackson
Scheduled by a contractor via Hello! on 04/16/2002 at 10:15:56. Contact: ###-####. okay to cover; dry sidewalls not complete they will leave this area uncovered; heads due in this week 4/16/2002 3:59:30 PM
INSP-Sprinkler Rough-in4/12/20024/12/20024/12/2002PFAIL
DetailsRick Jackson
Scott ###-#### soffits in kitchen/dining area are over 8 inches and will need pendants; laundry room soffits with heads too close to soffit; verify temp of furnace rooms may rewuire higher temp heads; draft stops require fire stopping; dry system not complete; need to complete wet system dry sidewall heads 4/12/2002 4:04:52 PM
INSP-Sprinkler Rough-in/Hydro4/8/20024/9/20024/9/2002ACANC
DetailsRick Jackson
Scheduled by a contractor via Hello! on 04/08/2002 at 09:43:48. Contact: ###-####. per Bill - no inspections on overhead; underground approved for install and overhead requires resubmittal 4/9/2002 11:00:38 AM
INSP-Sprinkler Rough-in/Hydro4/3/20024/5/20024/5/2002PNR
DetailsRick Jackson
Scheduled by a contractor via Hello! on 04/03/2002 at 16:42:17. Contact: ###-####. talked to Trent and he said they would be ready next week 4/5/2002 2:46:29 PM
INSP-Supply line flush4/3/20024/4/20024/4/2002APART
DetailsRick Jackson
Scheduled by a contractor via Hello! on 04/03/2002 at 16:41:31. Contact: ###-####. underground cover only - okay 4/4/2002 8:31:29 AM