INSP-Final Inspection | 10/11/2002 | 10/11/2002 | 10/11/2002 | A | PASS |
Troy Cobbley
|
|
|
fire alarm finaled
|
INSP-Final Inspection | 10/8/2002 | 10/10/2002 | 10/10/2002 | A | FAIL |
Troy Cobbley
|
|
|
provide an updated one line with the correct zone numbers for the fire inspector and provide the same for a building map 10/10/2002 10:47:12 AM
|
INSP-Final Inspection | 9/23/2002 | 9/24/2002 | 9/24/2002 | P | FAIL |
Troy Cobbley
|
|
|
strobe overspaced in n.e. corner of building #4, provide weatherproof listing for the A/V installed on the exterior wall, provide revised battery calculations for the a/v's since what is installed is not what was submitted, wire the circuits to match the plans submitted, clean up the wiring in the fire alarm panel, the inspection was stopped due to the problems listed above 9/24/2002 2:31:26 PM
|