Permit Information
Permit NumberFIR02-00211
StatusFinaled
Name WEIL J & CO
Site Address 5907 W CLINTON ST
Project NameJ. Weil Food Services
Customer Number 
ePlanReview 
Description
To replace the existing ADT Focus panel and replace it with a new Focus 200 panel. All existing devices are to be connected to the new panel including monitoring of the existing fire sprinkler riser. Two new sprinkler tamper switches are to be connected to the new fire alarm system. There is no associated building permit.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection8/21/20028/22/20028/22/2002APASS
DetailsTroy Cobbley
fire alarm system finaled 8/22/2002 1:00:31 PM
INSP-Final Inspection8/21/20028/21/20028/21/2002AFAIL
DetailsTroy Cobbley
after flow of water the alarms rang in 40 seconds but the exterior alarm bell did not operate and needs replaced.
INSP-Final Inspection8/15/20028/16/20028/16/2002PFAIL
DetailsTroy Cobbley
flow of water did not activate the inside horn or the outside alarm bell, still need to test the 4" butterfly vavle 8/16/2002 2:39:52 PM
INSP-Final Inspection7/5/20027/9/20027/9/2002AFAIL
DetailsTroy Cobbley
provide label in the fire alarm panel for the main breaker location, provide verification that the smoke detector is compatible with the fire alarm panel (its different from the cut sheets), block off spare outlet on the dedicated circuit, install correct orfice in the inspectors test outlet, test flow switch and 4" overhead valve, provide "knox box" 7/9/2002 2:35:28 PM