INSP-Final Inspection | 8/21/2002 | 8/22/2002 | 8/22/2002 | A | PASS |
Troy Cobbley
|
|
|
fire alarm system finaled 8/22/2002 1:00:31 PM
|
INSP-Final Inspection | 8/21/2002 | 8/21/2002 | 8/21/2002 | A | FAIL |
Troy Cobbley
|
|
|
after flow of water the alarms rang in 40 seconds but the exterior alarm bell did not operate and needs replaced.
|
INSP-Final Inspection | 8/15/2002 | 8/16/2002 | 8/16/2002 | P | FAIL |
Troy Cobbley
|
|
|
flow of water did not activate the inside horn or the outside alarm bell, still need to test the 4" butterfly vavle 8/16/2002 2:39:52 PM
|
INSP-Final Inspection | 7/5/2002 | 7/9/2002 | 7/9/2002 | A | FAIL |
Troy Cobbley
|
|
|
provide label in the fire alarm panel for the main breaker location, provide verification that the smoke detector is compatible with the fire alarm panel (its different from the cut sheets), block off spare outlet on the dedicated circuit, install correct orfice in the inspectors test outlet, test flow switch and 4" overhead valve, provide "knox box" 7/9/2002 2:35:28 PM
|