INSP-Final Inspection | 5/22/2003 | 5/22/2003 | 5/22/2003 | A | PASS |
Rick Jackson
|
|
|
|
INSP-Final Inspection | 5/20/2003 | 5/21/2003 | 5/21/2003 | A | FAIL |
Rick Jackson
|
|
|
this is grants cell. If we can do this at 8.00AM. Thank you Terry; Phone #: ###-#### Internet Inspection Request from: Terry Owsley need maps of initiating devices and Record of Completion; strobes synch'd 5/21/2003 7:49:40 AM
|
INSP-Final Inspection | 5/9/2003 | 5/13/2003 | 5/13/2003 | A | FAIL |
Rick Jackson
|
|
|
This is Grants cell. This needs to be done at 7:00 am. Have a great day.; Phone #: ###-#### Internet Inspection Request from: Terry Owsley not synchronized; maps with initiating devices; need better descriptors at FACP 5/13/2003 8:41:27 AM
|
INSP-Final Inspection | 5/5/2003 | 5/9/2003 | 5/8/2003 | A | CANC |
Rick Jackson
|
|
|
This is Grants Cell. Needs to be tested at 7:00 am if thats OK
Have a great day.; Phone #: ###-#### Internet Inspection Request from: Terry Owsley called Rob of Protex and told him I would not be able to do this inspection on 5/09 and he said he would reschedule for next week 5/8/2003 1:10:59 PM
|
INSP-Final Inspection | 4/24/2003 | 4/28/2003 | 4/28/2003 | A | NR |
Rick Jackson
|
|
|
This is grants Cell.
Thank you ; Phone #: ###-#### Internet Inspection Request from: Terry Owsley talked to Grant and they will reschedule when ready 4/28/2003 1:47:17 PM
|
INSP-Final Inspection | 4/22/2003 | 4/25/2003 | 4/24/2003 | A | CANC |
Rick Jackson
|
|
|
This is Grants Cell
Thanks Terry; Phone #: ###-#### Internet Inspection Request from: Terry Owsley Inspection cancelled from web by: Terry Owsley
|
INSP-Final Inspection | 2/21/2003 | 2/24/2003 | 2/24/2003 | A | NR |
Rick Jackson
|
|
|
Grant Ahten; Phone #: ###-#### Internet Inspection Request from: Terry Owsley per phone call from Rob this inspection won't be ready as they have determined that sprinkler control valves aren't supervised by the alarm panel; he will call when ready 2/24/2003 1:23:52 PM
|
INSP-Final Inspection | 2/7/2003 | 2/12/2003 | 2/12/2003 | A | FAIL |
Rick Jackson
|
|
|
Phone #: ###-#### Internet Inspection Request from: Terry Owsley inspection stopped due to: horns not working on all floors; strobes not in sync; south area of first floor devices not being recognized. Also need device location maps at FACP. Will need to test all devices, notification circuits; troubles; elevator recall; pump supervision - start test from scratch 2/12/2003 8:52:48 AM
|
FIR-Aging Inspection | 1/28/2003 | 1/28/2003 | 1/28/2003 | | NR |
Troy Cobbley
|
|
|
I spoke with Grant, who is with Protex and he stated that they were waiting for the elevators to get signed off before they called for inspection on the fire alarm system. He stated that the inspection would probably be called in next week 1/28/2003 9:40:20 AM
|