Information based on query as of Sunday, June 30, 2024.
Permit Information
Permit NumberFIR02-00244
StatusFinaled
Name TREASURE VALLEY FIRE PROTECTION
Site Address 1055 N CURTIS RD
Project NameSPR ST ALS-N TOWER
Customer Number 
ePlanReview 
Description
(ST ALPHONSUS-NORTH TOWER-2ND FLR)(PHARMACY) To remodel an existing fire sprinkler system in an 3,962 ft/2 office area, located on the 2nd floor, north tower for use as a 'pharmacy administration, receiving, breakdown, distribution & storage area for service to the overall hospital facility. Work is related to selective demolition and the new construction of interior non-bearing, non-combustible, fire-resistive walls for accessible restroom, conference room and work areas. The fire sprinkler system work shall comply with NFPA 13?1999, attached review comment and conditions list; as regulated by the fire chief. These notes, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to building permit: BLD02-01256.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection10/29/200210/29/200210/29/2002APASS
DetailsTroy Cobbley
INSP-Final Inspection9/20/20029/23/20029/23/2002APART
DetailsTroy Cobbley
temporary occupancy was given for the sprinkler system, with dave millers permission. Several sprinkler heads are spaced too close. When the owner occupies the storage cabinets will be built to the ceiling to separate sprinklers 9/23/2002 10:05:39 AM
INSP-Final Inspection9/10/20029/11/20029/11/2002AFAIL
DetailsTroy Cobbley
fire sprinkler piping is ok for cover but I could not final due to no ceiling tile being installed 9/11/2002 8:17:08 AM
INSP-Final Inspection8/29/20028/30/20028/30/2002AFAIL
DetailsTroy Cobbley
"work room" will be used as storage and therefore will be considered ordinary hazard occupancy which means the sprinkler pendants are overspaced. 130sq ft max. Also the shelves only allow 16" of clearance instead of the 18" required. The sprinklers will need to be space to the shelves 8/30/2002 2:34:31 PM