Permit Information
Permit NumberFIR02-00256
StatusFinaled
Name PEAK ALARM
Site Address 600 S 8TH ST
Project Namealm-Foothills School
Customer Number 
ePlanReview 
Description
Foothills School - To install a new fire alarm panel to replace two existing alarm control panels; connecting to new and existing alarm devices. The system includes manual pull stations, fire sprinkler system monitoring, duct detectors for HVAC air handler shut down, supplementary area smoke detection, a/v annunciation, and offsite monitoring.
The associated building permit (BLD 02-01092) is for Foothills School to construct a 658 sq. ft. class room and one 1714 sq. ft. music room (relocation from adjacent facility at 618 s. 8th) in an existing warehouse space. To include men and women toilet rooms.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection2/25/20032/28/20032/28/2003PPASS
DetailsRick Jackson
3:00
INSP-Final Inspection2/21/20032/25/20032/25/2003PCANC
DetailsRick Jackson
Scheduled by a contractor via Hello! on 2/21/2003 at 2:47:18 PM. Contact: ###-####. rescheduled for 2/28 at 3 pm 2/25/2003 12:22:05 PM
INSP-Final Inspection2/6/20032/7/20032/7/2003PFAIL
DetailsRick Jackson
Scheduled by a contractor via Hello! on 2/6/2003 at 11:50:07 AM. Contact: ###-####. tested duct detectors and all worked properly; need the following - new plans submitted for changes; map at remote annunciator with instructions; labels on rooftop cans indicating detectors inside cans; test panel for troubles etc; test sprinkler controls/flows; check NAC panels 2/7/2003 5:10:38 PM
INSP-Final Inspection1/23/20031/24/20031/24/2003PFAIL
DetailsTroy Cobbley
all spot smoke detectors and pull stations have been tested. The zone labeling for the smokes and the pull stations that are shown on the plans is incorrect and needs to be shown correctly on the as-built plans. No duct smoke detectors have been tested. One of the duct detectors in the south end of the building is installed correctly. All audio/visual devices were tested and functioned correctly. Smokes, pulls and A/V's are installed in the correct locations. No other devices have been tested including the NAC panels, FACP panel or fire sprinkler system devices. Review notes have not been looked at by me. 1/24/2003 3:57:34 PM
INSP-Conference9/17/20029/17/20029/17/2002PPART
DetailsRick Jackson
PHIL ; Phone #: ###-#### Internet Inspection Request from: Annette Moore due to numerous changes proposed by Phil Omas that resubmittals are required 9/17/2002 2:43:10 PM