Permit Information
Permit NumberFIR02-00286
StatusFinaled
Name SIMPLEX/GRINNELL
Site Address 11311 W CHINDEN BLVD
Project Namealm-HP-1South Service and 10M
Customer Number 
ePlanReview 
Description
HP-1South Service and 10M Chamber - To add manual pull stations and horn/strobes in buildings 1South Service and 10M Chamber, to meet current code. Also replacing old ZAM's and 4-wire circuits, with new IAM's and 2-wire circuits. There is no associated building permit.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection12/17/200212/20/200212/20/2002APASS
DetailsTroy Cobbley
###-#### Brad
INSP-Final Inspection11/7/200211/13/200211/13/2002PFAIL
DetailsTroy Cobbley
provide tamper switch on gate valve on fire pump test line, verify weather proof pull station assembly, provide hi/low pressure switch for anechoic chamber dry pipe valve 11/14/2002 1:42:18 PM