Permit Information
Permit NumberFIR02-00291
StatusFinaled
Name VIKING AUTOMATIC SPRINKLER CO
Site Address 190 E BANNOCK ST
Project NameSPR ST. LUKES PHASE 1
Customer Number 
ePlanReview 
Description
(PHASE 1 - St. Lukes RMC Fire Code Upgrade) To install a 6" and 3" "Ames ACV 115F" pressure reducing valves in series on a new bypass located off the existing basement fire pump in the "old" basement mechanical room. To install a separate 6" supply feed main in the basement for future separation/connection of high-pressure supplies to the CSP #3. Reference attached plans. This work is to reduce excessive (+175 lbs) pressure created by a previous installation/replaced fire booster pump with a 1000gpm @ 115lb rated fire booster pump (for the East Wing Tower Expansion, under the auspices of the State Fire Marshall's Office). Phase II work shall require separate permitting, plans and approval. The fire sprinkler system work shall comply with NFPA 13-1999, attached review comment and conditions list, as regulated by the Fire Chief. These notes, plans, permit and fire "Inspection Card" are required to be on site as a condition of this work, for witness of compliance verification of minimum code. This permit is not attached to a building permit.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection4/23/20034/23/20034/23/2003PPASS
DetailsRick Jackson
INSP-Sprinkler Rough-in/Hydro3/11/20033/13/20033/13/2003PPART
DetailsRick Jackson
brad; Phone #: ###-#### Internet Inspection Request from: Annette Moore hydro on new loop okay and high pressure 3/13/2003 1:30:32 PM
INSP-Sprinkler Rough-in/Hydro1/30/20032/5/20032/5/2003AFAIL
DetailsRick Jackson
8:30 will require hydrostatic test of all new piping; need alarm plan submittals for all new tampers 2/5/2003 11:05:57 AM
FIR-Aging Inspection1/30/20031/30/20031/30/2003 PART
DetailsRick Jackson
scheduled for 2/5/03 1/30/2003 12:37:15 PM
INSP-Final Inspection1/30/20031/30/20031/30/2003PCANC
DetailsRick Jackson
brad; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie rescheduled for 2/5 1/30/2003 12:49:34 PM