Permit Number | FIR02-00291 |
Status | Finaled |
Name |
VIKING AUTOMATIC SPRINKLER CO
|
Site Address |
190 E BANNOCK ST
|
Project Name | SPR ST. LUKES PHASE 1 |
Customer Number | |
ePlanReview | |
Description |
(PHASE 1 - St. Lukes RMC Fire Code Upgrade) To install a 6" and 3" "Ames ACV 115F" pressure reducing valves in series on a new bypass located off the existing basement fire pump in the "old" basement mechanical room. To install a separate 6" supply feed main in the basement for future separation/connection of high-pressure supplies to the CSP #3. Reference attached plans. This work is to reduce excessive (+175 lbs) pressure created by a previous installation/replaced fire booster pump with a 1000gpm @ 115lb rated fire booster pump (for the East Wing Tower Expansion, under the auspices of the State Fire Marshall's Office). Phase II work shall require separate permitting, plans and approval. The fire sprinkler system work shall comply with NFPA 13-1999, attached review comment and conditions list, as regulated by the Fire Chief. These notes, plans, permit and fire "Inspection Card" are required to be on site as a condition of this work, for witness of compliance verification of minimum code. This permit is not attached to a building permit.
|